Toshiba RAV-SM563UT-E Service Manual page 34

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

RAV-SM1403UT-E, RAV-SM1402BT-E, RAV-SM1402CT-E / RAV-SM1403AT-E
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
Height difference (m)
Outdoor unit
Outdoor unit
at upper side
at lower side
30
30
TD sensor
Accumulator
Rotary
(2500cc)
compressor
(DA420A3F – 21M)
(MPa)
Pd
Standard
3.52
Cooling
Overload
3.78
Low load
1.51
Standard
2.88
Heating
Overload
3.41
Low load
2.35
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Refrigerant pipe
at gas side Ø15.9
Ball valve
Outer dia. ØA
Strainer
TS sensor
4-way valve
(STF-0213Z)
Heat exchanger
Muffler
Outer side
Ø8, 2 rows, 20 steps
Ø25 × L210
FP1.3 flat fin
Inner side
Ø25 × L180
Ø9.52 row, 30 steps
FP1.5 flat fin
Pressure
Pipe surface temperature (°C)
(kg/cm²G)
Discharge
Ps
Pd
Ps
(TD)
0.85
35.9
8.7
87
1.12
38.6
11.4
84
0.71
15.4
7.2
40
0.60
29.4
6.1
85
1.08
34.8
11.0
81
0.24
24.0
2.4
80
Indoor unit
TCJ sensor
Strainer
Air heat exchanger
Section shape
of heat insulator
Outdoor unit
TO sensor
TE
sensor
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TE)
8
9
39
15
17
47
7
3
23
1
47
1
14
54
13
–19
40
–16
– 34 –
Revised : Mar. 2007
Distributor
(Strainer incorporated)
TC sensor
Refrigerant pipe
at liquid side Ø9.5
Min.
5m
Packed valve
Outer dia. ØB
PMV
(Pulse Motor Valve)
(UKV-25D22)
Strainer
Distributor
R410A 3.0kg
Indoor/Outdoor
Compressor
temp. conditions
Indoor
revolutions per
(DB/WB) (°C)
fan
second (rps)
Indoor
*
54
HIGH
27/19
45
HIGH
32/24
30
LOW
18/15.5
61
HIGH
20/–
24
LOW
30/–
73
HIGH
15/–
Max.
50m
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–10/(70%)