No.
Part name
ˆ
Compressor
1) Recover refrigerant gas.
2) Perform the works in 1 of
3) Remove the piping panel (Front).
4) Remove the piping panel (Rear).
5) Remove the sound-insulation plate.
6) Remove terminal cover of the compressor,
7) Remove TD sensor fixed to the discharge
8) Using a burner, remove pipe connected to
9) Pull out discharge pipe and suction pipe
10) Take off the compressor nuts (3 pcs)
11) Draw out the compressor toward you.
PMV coil
1. Detachment
1) Perform the works in 1 of
2) Hold outside of the coil by hands and turn
2. Attachment
1) Match the positioning extrusion of the coil
Procedure
Take off screws of the piping panel (Front)
and the base plate.
(ST1T Ø4 × 10, 2 pcs)
Take off screws of the piping panel (Front)
and the piping panel (Rear).
(ST1T Ø4 × 10, 2 pcs)
Take off screws of the piping panel (Rear)
and the base plate.
(ST1T Ø4 × 10, 2 pcs)
and then remove compressor lead and
case thermo. of the compressor.
(ST1T Ø4 × 10, 2 pcs)
pipe.
the compressor.
NOTE)
Pay attention that 4-way valve or PMV is
not exposed to a flame.
(Otherwise, a malfunction may be
caused.)
of the refrigerating cycle upward.
fixing the compressor to the base plate.
it while lifting upward. The fixing hooks
come off the fixing concavities and then
the coil can be removed from PMV body.
surely to the concave part of PMV body,
and then fix it.

ƒ
and in
.
TD sensor
Compressor lead

ƒ
Positioning extrusion
and in
.
– 156 –
Remarks
Piping panel (Front)
Piping panel
(Rear)
Remove (Suction pipe)
Remove (Discharge pipe)
Case thermo.
Compressor nuts
(3 pcs)
PMV body
PMV coil
Concave part

Hide quick links: