NOTE
It will be more convenient to open
the Service valve after removing
the Underside Clapboard.
SUCTION VALVE
LIQ. LINE VALVE
LIQUID-LINE FILTER-DRIER
(shipped loose for field installation)

1.2 LIMITATIONS

The unit should be installed in accordance with all National, State and Local Safety
Codes and the limitations listed below:
1.Limitations for the indoor unit, coil and appropriate accessories must also be observed.
2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is
the propeller type and is not designed to operate against any additional external static
pressure.
3.The maximum and minimum conditions for operation must be observed to assure a system
that will give maximum performance with minimum service.
4.The maximum allowable line length for this product is 150 feet.

2.0 GENERAL

The outdoor units are designed to be connected to a matching indoor coil with sweat
connect lines. Sweat connect units are factory charged with refrigerant for a match-
ing indoor coil plus 25 feet of field supplied lines.
Matching indoor coils are available with a thermostatic expansion valve or an orifice
for the most common usage. The orifice size and/or refrigerant charge may need to
be changed for some indoor-outdoor unit combinations, elevation differences or
total line lengths.
Before installation a load calculation must be performanced by the installer, as well
as a duct analysis. Proper sizing and coil/air handler matching are the installer's
responsibilities to ensure compliance.
Fig.1 Filter-Drier installation