Heat Controller RSGxxS-1D Series Installation, Operation & Maintenance Manual page 26

Rsgxxs-1d series, rsgxxr-1d series, hrgxxs-1d series split system a/c & heat pump-1.5 to 5 ton
Table of Contents

Advertisement

T1
T2
T3
CC
OFM
Fig.14 Outdoor Unit Wiring Diagram for A/C Systems(208/230V 3P 60Hz).
NOTE: Cut off the power supply when outdoor appear "POWER PHASE FAILURE".Swich on
power supply again after 10 seconds if correct wiring connected.
TABLE 4: Wiring Gauge for A/C Systems.
Model(Btu/h)
Input Current Fuse Amps
Line Quantity
Outdoor Unit
Power Line
Line Diameter
(AWG )
Line Quantity
Outdoor-Indoor
Signal Line
Line Diameter
(AWG )
Line Quantity
Thermostat
Signal Line
Line Diameter
(AWG)
All dimensions are in inches. They are subject to change without notice.
Certified dimensions will be provided upon request.
PLUG PLATE
WHITE
CN17
R
C
C
Y-OUT
D
LED1
O_FAN
G
CN6
YELLOW
Y
Y
CN13
TDC
B
CN7
W2
JUMP
CN10
1
0
INFAN
1
0
MANUAL DEFROST
T4
LPC
C
RV
T3
18000/24000
30000/36000
15/20
30/30
3
3
14
12
2
2
18
18
4
4
18
18
CC
COMPRESSOR CONTACTOR
COMP
COMPRESSOR
TDC
TIME DELAY CONTROL
T4
10K RESISTANCE.
T3
10K RESISTANCE.
L1
OFM
OUTDOOR FAN MOTOR
RC 1
OUTDOOR FAN MOTOR RUN CAPACITOR
GND
GROUND CHASSIS
L2
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
FACTORY
OPTIONAL
LOW
VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
FACTORY OPTIONAL
USE COPPER CONDUCTORS ONLY
WARNING
CABINET MUST BE PERMANENTLY
GROUNDED AND ALL WIRING TO CONFORM TO
I.E.C, N.E.C, C.E.C, C.L.C, AND LOCAL CODES AS APPLICABLE
REPLACEMENT WIRE MUST BE THE SAME GAUGE AND
INSULATION TYPE AS ORIGINAL WIRE.
STEADY ON = NORMAL OPERATION
0
OFF = TDC FAILURE
1 FLASH = T3 SENSOR FAILURE
1
2
2 FLASH = T4 SENSOR FAILURE
3
3 FLASH = LPC OPEN
4
4 FLASH = POWER PHASE FAILURE
MANUAL DEFROST
and
48000/60000
42000
40
40/50
3
3
12
10
2
2
18
18
4
4
18
18
24
JUMP
is unavailable for AC unit.