Initial Start Up And Checks Field Charging And Final Inspection - Heat Controller A-VFH24TA-1 Installation, Operation & Maintenance Manual

Inverterflex series outdoor ductless mini-split heat pumps
Table of Contents

Advertisement

Heat Controller
Electrical Work
Field Charging
Unit performance, efficiency, and life depends, to
a large extent, on a proper system charge. Time
spent on getting the charge right at start-up will
payoff in the long run. Operating conditions such
as voltage, air flow, evaporator coil size, and indoor
and outdoor temperature and humidity all have
an effect on the system pressures and superheat
conditions.
Units are factory charged before shipment. See
rating plate on outdoor unit for exact amount.
These units should be critically charged to ensure
proper performance. Some systems may require
additional charging of refrigerant, depending on
line set lengths. If the total line set length is less
than the amount in the table below, no additional
Fig. 19
KBTU/H
Total allowable length (for all indoor units)
18
24
30 / 36
42
VFH InverterFlex
refrigerant is needed.
If the total length or refrigerant lines for all models is
greater than the amount shown in the chart, additional
refrigerant is needed.
18 - 30 KBTU/H Units
Additional Refrigerant Charge = sum of additional line
length* ft (m) times 0.22 oz/ft (20g/m).
36 - 42 KBTU/H Systems
Additional Refrigerant Charge = sum of additional line
length* ft (m) times 0.24 oz/ft (22g/m).
*Additional line length is the sum of all the line sets
for all indoor units subtracted from the total allowable
length shown in the table.
32.8 ft. (10m)
98 ft. (30m)
131 ft. (40m)
166 ft. (50m)
21