Field Programming
2.1 S1 DIP Switch Settings on ACC-25/50 Series Motherboard
(ACC-MCB)
Switch 1 - Temporal pattern generated per ANSI S3.41 when Switch 1 is ON and Switches 2
and 3 are OFF
Switches 2 and 3 - used to determine what tone will be transmitted over the speakers before
and after the message is transmitted as well as the backup tone to be transmitted if the digital
voice generator fails.
Switch 4 - used to determine if the tone selected by S1 switches 2 and 3 will be generated
before the message is transmitted:
Switch 5 - used to determine if the tone selected by S1 switches 2 and 3 will be generated after
the message is transmitted:
NOTES: Tone Before/After only applies to Message 1 (Fire Evac). Messages 2 through 5 do not
generate a tone before or after the message.
Switches 6, 7 and 8 - used to determine the number of times the voice message will repeat.
SWITCH
All other settings for switches 6, 7 and 8 are invalid and will default to a message repeat of 3 times.
1 Some jurisdictions require tone evacuate only. This option prevents voice
36

S1 DIP Switch Settings on ACC-25/50 Series Motherboard (ACC-MCB)

OFF = No temporal pattern - tone generated as selected by Switches 2 and 3 (factory
default setting).
ON = 3 Cycles of Temporal pattern generated on steady tone. Switches 2 and 3 must be in
the OFF position.
SWITCH
SWITCH
2
3
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Table 2.5 Switch Settings for Tones
OFF = No tone before message
ON = Tone before message (factory default setting)
OFF = No tone after message (factory default setting)
ON = Tone after message
SWITCH
6
7
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
Table 2.6 Switch Settings for Message Repeat
messages from being generated. Verify with local AHJ if voice message is
allowed and the number of time the message may be repeated.
TONE TRANSMITTED BEFORE AND AFTER
DIGITAL VOICE MESSAGE
STEADY
SLOW WHOOP (factory default)
Hi-Lo
CHIME
SWITCH
NUMBER OF TIMES TO REPEAT DIGITAL VOICE
8
OFF
Tone Only, No Voice
OFF
OFF
OFF
ON
ON
INFINITE (until FACP trigger is reset)
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
MESSAGE
1
3
4
6 (factory default)
8