4.2
Cleaning the condensate trap and
syphon
V Remove the condensate trap (
V Clean the condensate trap with tap water and a brush.
V If required, place a new lip seal.
V Fill the condensate trap with water and reassemble.
V Undo the condensate drain connection (
item 1) and remove the syphon.
V Rinse and refit the syphon.
Buderus 500-24S - Subject to modifications resulting from technical improvements
fig. 73 and fig. 74).
fig. 73,
Fig. 73 Disconnect hose from condensate trap
Fig. 74 Remove the condensate trap
4
Maintenance
1
7215 3000-17.1TD
7215 3000-16.1TD
47