Circuits; Digital Alarm Communicator/Transmitter - Fire-Lite MS-9200UD User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9200UD:
Table of Contents

Advertisement

&LUFXLWV

1.4 Circuits

Reference
Manual

1.5 Digital Alarm Communicator/Transmitter

068' 31 $ 
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop,
configurable for NFPA Style 4, 6 or 7, provides communication to addressable
detectors, monitor (initiating device) and control (output device) modules. Refer to the
SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
24 VDC Resettable (smoke detector power) output - 0.5 amps maximum
24 VDC Nonresettable or Resettable power output - 0.5 amps maximum
24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY
card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The
fixed fail-safe relay monitors system trouble and the two programmable relays are
factory default programmed for system alarm and system supervisory. Contacts are
rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The
programmable relays can be programmed for the following operations:
fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
AC loss
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are
labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two
telephone line active red LEDs are provided as well as a green Kissoff LED. The
integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
rotary
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s).
The frequency and time duration of the tone(s) varies with the transmission
format. The control panel will adjust accordingly.
Communicate in the following formats:
✓ 12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
✓ 3 Touchtone Types
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
3URGXFW 'HVFULSWLRQ
Š
, programmable to