Circuits; Components - Fire-Lite MS-2 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-2:
Table of Contents

Advertisement

Product Description

1.4 Circuits

1.5 Components

14
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance
and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
Input Circuits
Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4
provide Style B (Class B) configurations. All IDCs accept I
conventional two-wire smoke detectors, four-wire smoke detectors and normally-open
contact devices.
Output Circuits
24 VDC resettable power output - 500 mA
24 VDC nonresettable power output (MS-4 only) - 500 mA
24 volt battery charger (up to 18 Amp Hour batteries)
Notification Appliance Circuits
One NAC (Notification Appliance Circuit) Style Y (Class B) on the MS-2
Two NACs Style Y (Class B) on the MS-4
Relays
Alarm Relay
Trouble Relay (fail-safe)
Supervisory Relay (MS 4 only)
Form-C contacts rated 2.0 amps @ 30 VAC (resistive)
Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary
components and wiring interface connectors. Optional modules plug in and are
mounted to the MS-4 main circuit board only.
Cabinet
The cabinet is red and the backbox measures 14.5" (36.8 cm) x 15.218" (38.65 cm) x
2.875" (7.3 cm) and provides space for two batteries (up to 7 Amp Hours). Also
available is an optional dress panel which mounts inside the cabinet.
Transformer Assembly
One 100VA transformer is provided standard with the FACP. An optional second
100VA transformer is available for the MS-4 to provide maximum accessory power.
Batteries
The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp
Hour, require use of a UL listed battery box such as the Fire•Lite BB-17F). Batteries
must be ordered separately.