Boiler
Gas Connections
Burner swing left or right

Burner Electrical Connections

26
(continued)
Vitocrossal 200 CM2 Installation Instructions
Note: For ease during burner maintenance, route the gas
supply pipe from the opposite side of the burner
hinges (otherwise the panel cannot be removed
when swinging burner left or right).
Legend
A Gas pipe
B Right front side panel
C Left front side panel
D Burner body
E Burner tube
1. Verify power cable connections L1 and N to boiler
control.
WARNING
Incorrect power connection can cause sever injuries
and / or damage to the appliance. Do not swap
connection L 1 and N.
2. Route the burner cables on the hinge side of the door
downwards behind right or left hand panel.
CAUTION
Never allow cables to come in contact with hot metal
components.
3. Insert burner plugs 41 and 90 into burner control.
4. Secure burner cables with cable ties to gaps in the
panel rails.