Venting Options - Stainless Steel / PP
Two Pipe System - Horizontal Exhaust / Horizontal Air Intake
The vent diameter of CM2 boilers can be reduced to 6" (150 mm) nominal vent size. See the following table for max.
vent length applicable to vent reduction diameter.
Model
Reduced Flue
vent
CM2-186
6" (150 mm)
CM2-246
6" (150 mm)
CM2-311
6" (150 mm)
46
Air-intake
to
pipe
7
7
6" (150 mm)
6" (150 mm)
6" (150 mm)
Vitocrossal 200 CM2 Installation Instructions
Flue
Min. 24 in.
(610 mm)
Air
a - Equivalent length (exhaust)
b - Equivalent length (air intake)
Max. Flue vent
Max. Air-intake
length "a"
pipe length "b"
65 ft. (20 m)
56 ft. (17 m)
Can not be reduced (See tables on page 42, 44)
Input derate %
0