Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
Graph 3
Target evaporating temperature control when "low humidity application + freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Note:
Te by LP sensor
Change
In order to increase continuous operation of the unit in low latent heat applications and avoid the
rise of temperature after thermostat OFF, the thermostat control will be changed when using
thermostat
field settings 16(26)-2-03 & 16(26)-2-04.
control
Thermostat ON
Thermostat OFF
Field Setting
Te target acceptable area
Te target
(˚C)
Te (see note) target acceptable area
Indoor temp. > setting → Te target down
Indoor temp. < setting → Te target up
RZQG Series
Trs ≥ 0.5 °C (No change from standard setting)
Trs ≤ -2.0 °C for 5 minutes continuously.
Trs ≤ 4.5 °C
Remote controller setting temp.
Te target limited ≤ 20˚C
(to protect the comp.)
Te target limited ≥ 2˚C
(not to freeze)
Freeze protection
(40min. integrated coil temp. ≤ -1˚C)
Field Setting from Remote Controller
Indoor Temp
(˚C DB)
69