Daikin SkyAir GQI-Eco Series Service Manual page 196

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Precautions for New Refrigerant (R-410A)
1. Flaring tool
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5 mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5 mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
186
Flare gauge
Specifications
Dimension A
Tube O.D.
Nominal size
Do
1/4
6.35
3/8
9.52
1/2
12.70
5/8
15.88
3/4
19.05
Differences
Change of dimension A
A
Class-2 (R-410A)
9.1
13.2
16.6
19.7
24.0
Dimension A
For class-1: R-407C
For class-2: R-410A
SiBE281013
Unit:mm
+0
−0.4
Class-1 (Conventional)
9.0
13.0
16.2
19.4
23.3
Appendix

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents