Daikin SkyAir GQI-Eco Series Service Manual page 137

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
A
Is there any
foreign matter around
the fan?
NO
Remove the fan motor connector.
Is the fan
rotatable easily by hand?
YES
CHECK 6
Check the resistance value for the fan
motor.
Is the
resistance value of the fan motor
normal?
YES
Does the fuse (F6U)
have continuity?
YES
Properly plug the fan motor connector
and then turn the power ON again.
Error is displayed?
NO
CHECK 6
Refer to P.172.
Service Diagnosis
YES
NO
NO
NO
YES
Troubleshooting by Remote Controller
Remove the foreign matter.
Replace the fan motor.
Replace the fan motor.
Replace the fuse.
Replace the outdoor unit
inverter PCB.
External factor (Noise, etc.)