Troubleshooting by Remote Controller
4.33 Transmission Error Between Remote Controller and
Indoor Unit
U5
Remote
Controller
Display
Applicable
All models of indoor unit
Models
Method of Error
The error is generated when the micro-computer detects that the transmission between the
indoor and the outdoor unit is not normal over a certain amount of time.
Detection
Error Decision
Normal transmission does not continue for specified period.
Conditions
Supposed
Causes
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Using
2-remote controllers
control.
NO
All indoor
PCB micro-computer
monitors blink.
YES
Replace the remote controller
Is it normal?
NO
Replace the indoor unit PCB, and
then restart.
Is it normal?
NO
156
Connection of two main remote controllers (when using 2 remote controllers)
Defective remote controller
Defective of indoor unit PCB
External factor (Noise, etc.)
YES
both remote controllers
returns to normal when
NO
the power is turned off
YES
YES
SS1 of
YES
is set to "MAIN."
NO
Operation
NO
momentarily.
YES
SiBE281013
Set one remote controller to "SUB";
turn the power supply off once and
then back on.
Replace indoor unit PCB.
There is possibility of error caused
by noise. Check the surrounding
area and turn on again.
Normal
Normal
There is possibility of error caused
by noise. Check the surrounding
area and turn on again.
Service Diagnosis