Daikin SkyAir GQI-Eco Series Service Manual page 57

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
3.2.29 Simulated Operation Function
A. Operation continues while the error code is displayed on the remote controller.
B. Operation continues even the error is detected. The remote controller displays error code
Note:
In case of a thermistor error other than A and B above, an abnormal stop is made and no
simulated operation is carried out.
Function and Control
In case of a thermistor error, simulated operation is performed in two different ways as
shown below even while the error is detected.
Applicable thermistors
· Outdoor air temperature thermistor
· Heat exchanger distribution pipe thermistor (in cooling)
· Intermediate heat exchanger thermistor (in heating)
· Liquid pipe thermistor
· Indoor suction air thermistor
· Indoor heat exchanger thermistor
only when the "Inspection/Test Run" button is pressed.
Applicable thermistors
· Remote controller thermistor
· Radiation fin thermistor
Applicable thermistors
· Suction pipe thermistor
· Discharge pipe thermistor
· Heat exchanger distribution pipe thermistor (in heating)
· Intermediate heat exchanger thermistor (in cooling)
Function Details
47