Figure 6. Typical Control Wiring used with TSA and TPA Outdoor Units.
Blower Motor Belt Tensioning Adjustment
1
PLACE BELT OVER ALL THREE
PULLEYS.
2
BELT TENSIONER
USING A 15/16" WRENCH ON
THE TENSIONER BODY NUT,
APPLY FORCE UNTIL MARKS
ALIGN AS SHOWN.
3
WHILE HOLDING THE TENSIONER IN
THIS POSITION, TIGHTEN THE
MOUNTING BOLT TO 23 FT−LBS USING A
9/16" WRENCH.
Figure 7. Typical Blower Belt Tensioner Adjustment Procedure