Bdc3 Blower Control; Adjusting The Blower Speed - Lennox CBA25UHV Installation Instructions Manual

Air handler units
Hide thumbs Also See for CBA25UHV:
Table of Contents

Advertisement

BDC3 Blower Control

JP1 15 PIN
PLUG (BOARD
TO MOTOR)
QC1
24V ACCESSORY
SERVICE
CONTACTS –
RATED FOR 1 AMP
24V/1A
OR LESS
QC2
NORM
+
OPERATIONAL
-
SELECTOR PINS
(AFFECTS BOTH
TEST
HEATING AND
ADJUST
COOLING MODES)
HEATING SPEED
SELECTOR PINS
COOLING SPEED
SELECTOR PINS
FIGURE 16. BDC3 Variable Speed Control Selections
Merit
CBA25UHV units are equipped with a vari-
®
able-speed motor that is capable of maintaining a spec-
ified CFM throughout the external static range. A particu-
lar CFM can be obtained by positioning jumpers (COOL,
HEAT, and ADJUST) on the BDC3 control.
The jumpers are labeled 1, 2, 3, and 4. This indicates
the selected air volume (CFM). The ADJUST jumper is
labeled Test, -, +, and Norm. The - and + pin settings are
used to add or subtract a percentage of the CFM select-
ed. The Test jumper is used to operate the motor in the
test mode. The delay jumper controls the timing pattern in
which the fan delay occurs.
Figure 23 illustrates the BDC3 control. Use either table 5
on page 19, or table 6 on page 19, to determine the cor-
rect air volume for heat and cool speed taps.
Diagnostic LEDs located on the BDC3 control to assist in
servicing the unit. Read the jumper settings section before
adjusting blower speed. Refer to figure 23 on page 17 for
identification.

Adjusting the Blower Speed

Diagnostic LEDs
1 - RUN LED indicates there is a demand for the blower
motor to run.
2 - CFM LED indicates the cubic feet per minute at
which the unit is operating. The light flashes once
for approximately every 100 CFM. For example, if
the unit is operating at 1000 CFM, CFM LED will
flash 10 times. If the CFM is 1150, CFM LED will
flash 11 full times plus one fast or half flash.
At times, the light may appear to flicker or glow. This is
normal and occurs when the control is communicating
with the motor between cycles.
Move the jumper pins to select the blower speed needed
to meet application CFM requirements.
JP1
4
4
4
3
3
3
2
2
2
1
1
1
HEAT
COOL
DELAY
CFM RUN
DIAGNOSTIC
LEDS
FAN DELAY
SELECTOR PINS
JUMPER SETTINGS
Before changing jumper setting, make sure the motor
has completely stopped. Any jumper setting change will
not take place while the motor is running.
Table 2 lists the recommended factory blower speed tap
selections for Merit
tings are for nominal tonnage match-ups with the Merit
CBA25UHV. When matched with other sizes, it is rec-
ommended that the CFM be adjusted to provide approxi-
mately 400 CFM per ton.
TABLE 2. Recommended Blower Speed Taps
Air Handler
CBA25UHV018
CBA25UHV024
CBA25UHV030
CBA25UHV036
CBA25UHV042
CBA25UHV048
CBA25UHV060
NOTES -
1 - Condensing Unit
2 - Heat Pump
3 - Condensing Unit with electric heat only
4 - Heat Pump with electric heat
* Minimum setting for heat
To change jumper positions, gently pull the jumper off the
pins and insert it onto the desired set of pins. The following
section outlines the different jumper selections available
and conditions associated with each one as illustrated in
figure 16.
After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in the appropriate tables on the following pages. From the
tables, determine which row of CFM volumes most closely
matches the desired CFM. Once a specific row has been
chosen (+, NORMAL, or -), CFM volumes from other rows
cannot be used. Below are descriptions of the jumper se-
lections.
ADJUST JUMPER
The ADJUST pins allow the motor to run at normal speed,
slightly higher (approximately 10%) than normal speed,
or slightly lower (approximately 10%) than normal speed.
Page 16
IMPORTANT
CBA25UHV series units. These set-
®
Speed Tap Selection
Cooling
Heating*
Note 1 -
Note 2 -
Note 3 -
COOL
COOL
HEAT
PIN #2
PIN #2
PIN #2
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
COOL
COOL
HEAT
PIN #3
PIN #3
PIN #3
®
Note 4 -
HEAT
PIN #2
HEAT
PIN #3
HEAT
PIN #3
HEAT
PIN #3
HEAT
PIN #3
HEAT
PIN #3
HEAT
PIN #3