Slant/Fin Galaxy GXH-300H Installation And Operating Instructions Manual

Gas-fired cast iron boilers for natural and l.p. propane gases
Hide thumbs Also See for Galaxy GXH-300H:

Advertisement

GAS-FIRED CAST IRON BOILERS FOR NATURAL AND L.P . PROPANE GASES
GALAXY
INSTALLATION AND OPERATING INSTRUCTIONS
CONTENTS ...........................................................................PAGE
Ratings, Dimensions, Data...........................................................2
Boiler Location........................................................................ 3
Boiler Foundation.................................... ............................... 3
Chimney Requirements.......................................................... 3
Minimum Clearance.................................. .................................. 3
Vent Piping.............................................................................. 4
Gas Piping............................................. ...................................... 4
Electrical Controls and Wiring................................................ 5
Boiler Room Air Supply and Ventilation................................. 5
Draft Hood Installation............................................................ 6
Piping at Boiler-Water Boilers................... ........................... 6
Steam Controls Assembly and Installation............................ 6
Piping a Steam Boiler.......................................................... 6,7
Vent Damper.......................................... .............................. 8,9
Filling and Venting Water Systems.............. .......................... 9
Burner Adjustment, Checking Gas Input...... ....................... 13
Controls, Safety Check......................................................... 14
Low Water Cut-off Check-Out ................................................... 14
Pressure Control Check-Out ..................................................... 14
Blowing Off a Steam Boiler........................ ............................... 15
Care and Maintenance.............................................................. 16
Safety Check for Control System......................................... 17
Protection From Freezing..................................................... 17
Water Treatment..................................... .............................. 17
Sequence of Operations............................... ...................... 18, 19
Troubleshooting Guide...............................................................21
Appendix A ................................................................................ 22
Appendix B & C......................................................................... 23
Appendix D & E ..........................................................................24
Heating Contractor
Address
Phone Number
HOT WATER-Models GG-75H through GG-399H
LOW PRESSURE STEAM AND HOT WATER- Models GXH-105 through GXH-300H
and Models GX-225 and GX-250
WARNING
LIQUEFIED PETROLEUM (L.P .)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph entitled
"LIQUEFIED PETROLEUM (L.P .) PROPANE GAS-FIRED
BOILER LOCATION" on page 4 of this instruction book.
The above warning does not apply to NATURAL gas-
fired boilers.
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1-
CSA B149.1-00 for natural gas and
latest edition or
propane
. The installation must also conform to the
additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having jurisdic-
tion, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, No. CSD-1 or
B149.1-00 for natural gas and propane
conflict in the above requirements, then the more stringent
requirement will apply.
This manual must be left with owner and should be hung on
or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed,
connected, serviced and repaired by a trained, experienced
service technician, familiar with all precautions required for
gas-fired equipment and licensed or otherwise qualified, in
compliance with the authority having jurisdiction.
®
Boiler Model Number
Boiler Serial Number
Installation Date
Printed in Canada 01/07
Part No. 41-0549
CSA
. If there is any
PUBLICATION GG-40
Rev. K

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin Galaxy GXH-300H

  • Page 1: Table Of Contents

    . The installation must also conform to the Steam Controls Assembly and Installation......6 additional requirements in this Slant/Fin Instruction Book. Piping a Steam Boiler............6,7 Vent Damper................ 8,9 Operating Instructions: In addition, where required by the authority having jurisdic- Filling and Venting Water Systems....
  • Page 2: Ratings, Dimensions, Data

    GALAXY Pressure Relief Valve 19 mm ( ") 13 mm ( Vent Tapping Alternate 38 mm (1-1/2") return (except GG-75 thru GG-175 FRONT VIEW RIGHT SIDE RIGHT SIDE RIGHT SIDE All GG and GXH GG / GXH-PT GXH-PZT-PPZT GXH-PZ GG SERIES HOT WATER BOILERS—DIMENSIONS IN MM FOLLOWED BY INCHES GG-75H GG-100H GG-125H...
  • Page 3: Installation Requirements

    This installation must also conform to the additional require- ments in this Slant/Fin instruction book. Installation and service codes and other authorities having jurisdiction. to be performed by a qualified installer, service agency or the If a masonry chimney is exposed to the outdoors on one or gas supplier.
  • Page 4: Vent Piping

    GALAXY E. All venting means should be inspected frequently. See Care GALAXY GXH SERIES and Maintenance and separate User's Information Manual. GAS PIPING— MODELS GXH-105 MODELS GXH-210 TO A. Local installation codes apply. The pipe joint compound used on THROUGH GXH-190 GXH-300H, GX-225 TO threads must be resistant to the action of liquefied petroleum gases.
  • Page 5: Electrical Controls And Wiring

    GALAXY than maximum pressure when the boiler or any other appliance is of the National Fuel Gas Code, ANSI Z223.1-latest edition or turned on or off. CSA B149.1-00 for natural gas and propane, or applicable pro- ELECTRICAL CONTROLS AND WIRING visions of the local building codes.
  • Page 6: Draft Hood Installation

    2. PUMP LOCATION — Locating low-head pump(s) on Notes: return to boiler is acceptable for smaller boiler sizes in A. Slant/Fin makes no recommendation, nor does Slant/Fin residences of one or two stories. The alternate pump imply that One Pipe Parallel and Counterflow Gravity...
  • Page 7 Pipe sizes shown above for Hartford Loop are recommended by Slant/Fin. However, certain local codes may require larger pipe sizes. Counter flow piping is sized one pipe size larger than a parallel flow piping. Consult with local authorities.
  • Page 8: Vent Damper

    Slant/Fin gas boiler models. These boilers must also be equipped with a plate which states that the boiler must or may be used with a Slant/Fin automatic vent damper device and indicates the proper vent damper model number. This device cannot be used with a millivolt ignition system.
  • Page 9: Operating Instructions

    FILLING AND VENTING WATER SYSTEMS 4. All Slant/Fin Galaxy steam boilers equipped with inter- A. Fill the system with water. Vent or purge off air. mittent pilot ignition and continuous (standing) pilot B.
  • Page 10: Initial Start, Safety And Lighting Instructions

    GALAXY CLEAN STEAM BOILER SYSTEM Be sure to smell next to the floor because some gas is heavier A. Fill the boiler to water line indicated on the boiler. than air and will settle on the floor. B. Follow start-up procedure for boiler and operate the boiler WHAT TO DO IF YOU SMELL GAS with steam in the entire system for 2 or 3 days to bring oil •...
  • Page 11 GALAXY – If knob does not pop up when released, stop and imme- 2. Continuous Burning Pilot (24V). diately call your service technician or gas supplier. FOR BOILERS EQUIPPED WITH HONEYWELL GAS VALVE – If the pilot will not stay lit after several tries, turn the gas VR8200, VR8300, V8200 or V800.
  • Page 12 GALAXY 4. Intermittent Pilot System (IID). Operating Instructions 1. STOP! Read the safety information above on this page. FOR BOILERS EQUIPPED WITH HONEYWELL GAS VALVE 2. Set the thermostat to lowest setting. VR8204 or VR8304 (see figures 13 and 14). 3.
  • Page 13: Burner Adjustment, Checking Gas Input

    (For 1050 Btu/cu.ft. gas, this becomes: Input = cu. ft. metered in 3 minutes × 1050 × 20) 5. The higher heating value* of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Service Dept. for re-orificing procedures if any of the following apply:...
  • Page 14: Controls, Safety Check

    GALAXY C.Main Burner Ignition Check-out and Pilot Adjustment 3. Refill the boiler and repeat test. 1. The pilot flame must not smother or snuff out when 4. Refill the boiler and reset controls for normal operation. tested as follows: B. Float type low water cut-off i.
  • Page 15: Blowing Off A Steam Boiler

    GALAXY skimmer plug slowly and carefully. Install 19 mm (3/4") 5. Fittings skimmer valve, elbow and length of pipe and place a 6. Instruction sheet and assembly drawing. bucket underneath the open end of the pipe. Cover 7. Steam safety valve and 19 mm ( ") street coupling.
  • Page 16: Care And Maintenance

    GALAXY pop safety valve and re-pipe boiler as shown in Figure B 6. WATER SYSTEM: check: below, making sure to reinstall pop safety valve on tee to i. System to be full of water, and pressure to remain sta- complete the blow off connection. ble at correct setting on gauge.
  • Page 17: Safety Check For Control System

    GALAXY d. Clean and replace burners* and pilot. Adjust burners as PROVIDING PROTECTION FROM FREEZING. described on page 13. Anti-freeze is sometimes used in hydronic heating systems to * To clean burners run a clean flue brush up the tube protect against freeze-up in the event of until all foreign matter is removed.
  • Page 18: Sequence Of Operations

    GALAXY SEQUENCE OF OPERATION FOR GALAXY BOILERS EQUIPPED WITH CONTINUOUS BURNING PILOT (HONEYWELL OR WHITE RODGERS) LIGHTED PILOT HEATS THERMOCOUPLE AND KEEPS PILOTSTAT OPEN. THERMOSTAT CALLS FOR LOW LIMIT (FOR TANKLESS COIL) HEAT CALLS FOR HOT WATER HIGH-LIMIT CONTACTS CLOSED? NO FURTHER LOW WATER CUT-OFF (WHEN USED) CONTACTS CLOSED? ACTION...
  • Page 19 GALAXY SEQUENCE OF OPERATION FOR SLANT/FIN BOILERS EQUIPPED WITH WHITE RODGERS INTERMITTENT IGNITION SYSTEM THERMOSTAT CALLS FOR LOW LIMIT (FOR TANKLESS COIL) HEAT CALLS FOR HOT WATER RELAY ENERGIZES VENT DAMPER CIRCULATOR ENERGIZED WHEN IF INCLUDED USED WITH COMBINATION AQUA-...
  • Page 20: Pump Or Valve Zoning Of Water Boilers

    GALAXY PUMP OR VALVE ZONING OF WATER BOILERS COMBINATION CONTROLS WITH T TV Z TERMINALS* L8148- TO ADDITIONAL L8124 R845A RELAYS FOR OTHER ZONES R845A RELAYS ZONE 1 V8043F V8043F V8043F JUMPER SHOWN LOW VOLTAGE GAS VALVE L8148- LOW VOLTAGE L8124 THERMOSTAT POWER SUPPLY.
  • Page 21: Troubleshooting Guide

    GALAXY BURNERS FAIL TO OPERATE CAUSE REMEDY 1. Safety pilot out, or flame too low. 1. Check, clean, re-light. See instructions. 2. Gas supply valve shut off. 2. Open gas valve(s). 3. Electric switch open. 3. Close switch. 4. Blown or defective line fuse. 4.
  • Page 22: Appendix A

    GALAXY APPENDIX A Removal of Existing Boiler from Common Vent System "At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation."...
  • Page 23 GALAXY APPENDIX B Thermostatic Bypass Valve Thermostatic bypass valves type TV are designed to allow established. If flow is already to the system, no adjustment boilers to reach their optimum operating temperature is required. quickly and to prevent cool/cold return temperatures from Return Mounting: On the return "TV"...
  • Page 24 Use of Non-oxygen Diffusion Barrier Underfloor Tubing The boiler warranty does not cover leaks resulting from with a heat exchanger, Slant/Fin recommends the use of corrosion caused by the use of underfloor plastic tubing underfloor plastic tubing with an oxygen diffusion barrier.