Mitsubishi Electric Mr.Slim PAR-30MAA Technical Manual page 73

Ma remote controller
Hide thumbs Also See for Mr.Slim PAR-30MAA:
Table of Contents

Advertisement

«Important»
Do not install the controller in a place where the difference
between the remote controller surface temperature and the
actual room temperature will be great.
If the temperature difference is too high, room temperature
may not be adequately controlled.
To reduce the risk of shorting, current leakage, electric
shock, malfunctions, smoke, or fire, do not install the con-
troller in a place exposed to water or in a condensing envi-
ronment.
(2) Installation space
Leave a space around the remote controller as shown in the figure at right,
regardless of whether the controller is installed in the switch box or directly
on the wall. Removing the remote controller will not be easy with insufficient
space.
Also, leave an operating space in front of the remote controller.
4. Installation / Wiring work
(1) Installation work
Controller can be installed either in the switch box or directly on the wall.
Perform the installation properly according to the method.
Drill a hole in the wall.
■ Installation using a switch box
• Drill a hole in the wall, and install the switch box on the wall.
• Connect the switch box to the conduit tube.
■ Direct wall installation
• Drill a hole in the wall, and thread the cable through it.
Seal the cable access hole with putty.
■ Installation using a switch box
• Seal the remote controller cable access hole at the connection of
switch box and conduit tube with putty.
To reduce the risk of electric shock, malfunctions, or fire, seal
the gap between the cables and cable access holes with putty.
Prepare the bottom case of the remote controller.
Connect the remote controller cable to the terminal block on the bottom case.
Peel off 6 mm of the remote controller cable sheath as shown in the figure below, and thread the cable from behind the bot-
tom case. Thread the cable to the front of the bottom case so that the peeled part of the cable cannot be seen behind the
bottom case. Connect the remote controller cable to the terminal block on the bottom case.
Thread the sheath part
of the cable to the front.
Sheath
10 (13/32)
Front
6 (1/4)
Thread the cable.
unit: mm(in)
Back
To avoid deformation and malfunction, do not install the
remote controller in direct sunlight or where the ambient
temperature may exceed 0°C (10°F) or drop below 0°C
(32°F).
Minimum required space
around the remote
controller
Wall
Bushing
Front cover and top case
2-core wire must not
be seen on the back.
External dimensions of
remote controller
30 (1-3/16)
30
(1-3/16)
Temperature
sensor
120 (4-3/4)
unit: mm(in)
Conduit tube
Locknut
Switch box
Seal the gap
with putty.
Remote
controller cable
Bottom case
Connect the cable.
(non-polarized)
Connect the cable so
that the cable sheath
is not pinched.
30
(1-3/16)
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents