Mitsubishi Electric Mr.Slim PAR-30MAA Technical Manual page 61

Ma remote controller
Hide thumbs Also See for Mr.Slim PAR-30MAA:
Table of Contents

Advertisement

Meaning of "Function setting"
Mode02 : indoor temperature detecting
No
indoor temperature (ta)
Average data of the sen-
No.1
sor on all the indoor units
The data of the sensor
on the indoor unit that
No.2
connected with remote
controller
The data of the sensor on
No.3
main remote controller.
*Can be set only when a wired remote controller is used. This function cannot be set for floor type models.
When using 2 remote controllers (two-remote controller operation), the remote controller with built-in sensor must be set as a
main remote controller.
Supplementary Information (Unit Function Setting)
(For setting, refer to OUTDOOR UNIT'S SERVICE MANUAL.)
1) Vane setting (Function setting mode11)
Model
Setting No.
1
PLA-BA(2)(3)
2
3
1
PCA-KAQ
2
3
*Be careful of the smudge on ceiling.
2) Vane differential setting in heating mode (cold wind prevention) (Function setting mode14)
When piping temperature (TH5) becomes low during heating operation, the up / down vane is set to horizontal direction for
less draft setting.
In this vane differential setting, the conditions of piping temperature to change airflow setting of horizontal and setting shown
below can be adjusted finely.
Setting 1 (low) • • • 24˚C
Setting 2 (standard) • • • 28˚C
Setting 3 (high) • • • 32
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
Intial
ta = (A+B) / 2
setting
ta = A
ta = C
: Initial setting
Downward position than the standard (less smudging setting)
Standard position
Upward position than the standard (less draft setting) *
No vane function
Standard position
Upward position than the standard (less draft setting) *
28˚C
32˚C
38˚C
OUTDOOR
OUTDOOR
INDOOR
INDOOR
INDOOR
REMOTE
REMOTE
REMOTE
(MAIN)
(SUB)
(MAIN)
ta = (A+B) / 2
ta = A
ta = B
ta = A
ta = C
ta = C
Setting
Setting airflow
Horizontal airflow
Piping temperature (TH5) (˚C)
OUTDOOR
INDOOR
REMOTE
REMOTE
(SUB)
(MAIN)
ta = A
ta = A
ta = C
61