Mitsubishi Electric MAC-821SC-E Installation Manual

Hide thumbs Also See for MAC-821SC-E:

Advertisement

Centralized On-Off Remote Controller
MAC-821SC-E
[FOR INSTALLER]

INSTALLATION MANUAL

[FÜR INSTALLATEURE]
INSTALLATIONSHANDBUCH
[POUR L'INSTALLATEUR]
MANUEL D'INSTALLATION
[VOOR DE INSTALLATEUR]
INSTALLATIEHANDLEIDING
[PARA EL INSTALADOR]
MANUAL DE INSTALACIÓN
[PER L'INSTALLATORE]
MANUALE DI INSTALLAZIONE
[°π∞ ∞À∆√¡ ¶√À ∫∞¡∂π ∆∏¡ ∂°∫∞∆∞™∆∞™∏]
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
[PARA O INSTALADOR]
MANUAL DE INSTALAÇÃO
[TIL INSTALLATØREN]
INSTALLATIONSMANUAL
[FÖR INSTALLATÖREN]
INSTALLATIONSMANUAL
[MONTÖR ‹Ç‹N]
MONTAJ ELK‹TABI
[ДЛЯ УСТАНОВИТЕЛЯ]
РУКОВОДСТВО ПО УСТАНОВКЕ
[
]
[
]
English
Deutsch
Français
Nederlands
Español
Italiano
∂ÏÏËÓÈο
Português
Dansk
Svenska
Türkçe
Русский

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MAC-821SC-E

  • Page 1: Installation Manual

    Centralized On-Off Remote Controller MAC-821SC-E [FOR INSTALLER] INSTALLATION MANUAL English [FÜR INSTALLATEURE] Deutsch INSTALLATIONSHANDBUCH [POUR L’INSTALLATEUR] MANUEL D’INSTALLATION Français [VOOR DE INSTALLATEUR] INSTALLATIEHANDLEIDING Nederlands [PARA EL INSTALADOR] MANUAL DE INSTALACIÓN Español [PER L’INSTALLATORE] MANUALE DI INSTALLAZIONE Italiano [°π∞ ∞À∆√¡ ¶√À ∫∞¡∂π ∆∏¡ ∂°∫∞∆∞™∆∞™∏] E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™...
  • Page 2 MAC-821SC-E ERRATA The following corrections have been made to the MAC-821SC-E INSTALLATION MANUAL. 2. Accessory The list of items to prepare at the installation site and the illustrations have been revised. Items to Prepare at the Installation Site MA & Contact terminal interface...
  • Page 3: Table Of Contents

    Caution To use this centralized controller, you must have a MA & Contact Terminal Interface (MAC-397IF-E, sold separately) for each air conditioner unit. Contents 1. Safety Instructions .......................... 2 2. Accessory ............................3 3. Mounting the Centralized Controller/Direct Wiring ................6 4.
  • Page 4: Accessory

    2. Accessory Before installing the unit, make sure that you have all the necessary parts. Centralized controller A Cover Remove the cover with a flathead screwdriver. B Screw Base plate Switch box Room name stickers Rubber seal (large) Rubber seal (small) Sealing material (adhesive) Mounting screw M4 ×...
  • Page 5: Cover

    50/60 Hz Air conditioner Ground Indoor unit MAC-821SC-E MAC-397IF-E * Connect the power switch with gap of 3 mm or more when open to interrupt the source power phase. (When the power switch is shut off, it must interrupt all phases.) 2-2.
  • Page 6 2-5. Sample Configuration This figure shows a sample 4-unit configuration. Connection wire C (max. length of 100 m) A/C Device No. 3 A/C Device No. 2 Power supply ~/N 220–240 V 50/60 Hz A/C Device No. 1 A/C Device No.4 Centralized controller 1 A MA &...
  • Page 7: Mounting The Centralized Controller/Direct Wiring

    3. Mounting the Centralized Controller/Direct Wiring 3-1. Mounting Preparations Remove 2 screws, and remove the base plate 2 from the switch box 3. Set the 2 screws aside, as they will be used in the section on “4-1. Mounting the Base Plate” under “Mounting the Centralized Controller”. Screw M4 Insert the switch box 3 into the wall.
  • Page 8 3-2. Connecting the Connection Wire Connect the power supply wire (2-core + ground) B to the power terminal. After they are connected, check that the wires cannot be easily pulled off. Power terminal Power supply wire B Work on Power Supply wire End Washer (2-core + ground) •...
  • Page 9: Mounting The Centralized Controller

    4. Mounting the Centralized Controller 4-1. Mounting the Base Plate Insert the base plate 2 into the switch box 3, and remount it using the screws removed in the “3-1 Mounting Preparations”. Be sure to mount the base plate 2 so the up arrow is facing Up arrow upward.
  • Page 10: Test Run

    Select the appropriate stickers from the room name stickers 4 supplied, and affix them to the display section of the panel. Room name stickers 4 7. Specifications Model MAC-821SC-E No. of controlled air conditioners 8 units Power ~/N, 220–240 V, 50/60 Hz...
  • Page 11 This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is based on • Low Voltage Directive 73/23/EEC the following EU regulations: • Electromagnetic Compatibility Directive 89/ 336/EEC HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN SG79Y547H01 Printed in Japan...

Table of Contents