<Request Cord list>
* The Request code 150 – 152 data is the information for the indoor unit to which the remote controller is connected.
Request
code
0
Operation state
1
Compressor - Operating current (rms)
2
Compressor - Accumulated operating time
3
Compressor - Number of operation times

Discharge temperature (TH)
5
Outdoor unit - Liquid pipe 1 temperature (TH3)
7
Outdoor unit - 2 phase pipe temperature (TH6)
9
Outdoor unit - Outside air temperature (TH7)
10
Outdoor unit - Heatsink temperature (TH8)
12
Discharge superheat (SHd)
13
Sub - cool (SC)
16
Compressor - Operating frequency
18
Outdoor unit - Fan output step
22
LEV (A) opening
30
Indoor unit - Setting temperature
Indoor unit - Intake air temperature
31
<Measured by thermostat>
37
Indoor unit - Liquid pipe temperature (Unit No.1)
38
Indoor unit - Liquid pipe temperature (Unit No.2)
39
Indoor unit - Liquid pipe temperature (Unit No.3)
0
Indoor unit - Liquid pipe temperature (Unit No.)
2
Indoor unit - Cond./ Eva. pipe temperature (Unit No.1) -39 – 88
3
Indoor unit - Cond./ Eva. pipe temperature (Unit No.2) -39 – 88

Indoor unit - Cond./ Eva. pipe temperature (Unit No.3) -39 – 88
5
Indoor unit - Cond./ Eva. pipe temperature (Unit No.) -39 – 88
Outdoor unit - Error postponement history 1 (latest)
100
103
Error history 1 (latest)
10
Error history 2 (Second to last)
107
Operation mode at time of error
150
Indoor - Actual intake air temperature
151
Indoor - Liquid pipe temperature
152
Indoor - 2 phase pipe temperature
68
Request content
Description (Display range)
Refer to "Operation mode"
0 – 50
0 – 9999
0 – 9999
3 – 217
-0 – 90
-39 – 88
-39 – 88
-0 – 200
0 – 255
0 – 130
0 – 255
0 – 10
0 – 500
17 – 30
8 – 39
-39 – 88
-39 – 88
-39 – 88
-39 – 88
Displays postponement code
("--" is displayed if no postpone-
ment code is present)
Displays error history
("--" is displayed if no history is
present)
Displays error history
("--" is displayed if no history is
present)
Displayed in the same way as
request code "0"
-39 – 88
-39 – 88
-39 – 88
Unit
Remarks
A
10 hours
100 times
˚C
˚C
˚C
˚C
˚C
˚C
˚C
Hz
Step
Pulses
˚C
˚C
˚C
˚C
˚C
"0" is displayed if
˚C
the target unit is
˚C
not present
˚C
˚C
˚C
Code
Code
Code
˚C
˚C
˚C

Hide quick links: