Recircula on Mode
Sequence of Opera on 
DIP switches (SW2 ‐ white switches, #4, #8) should be 
set correctly for recircula on and mode.  The Rinnai 
water heater should be turned on. 
Pump recircula on begins when the water heater is 
turned on.  The Rinnai inlet and outlet thermistors 
measure the water temperature.  
The water heater produces hot water at the 
temperature se ng.  If the inlet thermistor detects 
abnormal temperature then diagnos c code 51 is 
generated and the pump will turn off. 
When the return water temperature reaches 
approximately 15°F (8.3°C) below the temperature 
se ng, the water heater and pump will turn off. 
The cycle will restart at the approximate  me interval 
in the table based on the temperature thermistor 
readings. 
Economy Mode 
The Economy mode operates as follows: 
Less energy consumed due to fewer pump cycles 
Assumes plumbing is insulated (minimal pipe heat 
loss)  
Pump cycles on every 31 to 79 minutes (see 
table). 
Comfort Mode 
The Comfort mode operates as follows: 
Higher energy consump on due to more pump 
cycles 
Assumes plumbing is not insulated resul ng in 
higher pipe heat loss  
Pump cycles on every 15 to 39 minutes (see 
table). 
30 
 
KB Series Manual 
Typical Pump ON Intervals* 
Rinnai 
Temperature 
Se ng 
°F 
140 
135 
130 
125 
120 
115 
110 
108 
106 
104 
102 
100 
98 
*  The pump will cycle on at these calculated 
intervals which are based on the temperature 
se ng, insula on, and es mated heat loss in the 
system.  The values for your installa on may vary. 
(minutes) 
Economy 
Comfort 
Mode 
Mode 
31 
15 
31 
15 
31 
15 
31 
15 
31 
15 
35 
18 
42 
21 
45 
22 
49 
24 
54 
27 
60 
30 
68 
34 
79 
39 