BLOWER PERFORMANCE SPECIFICATIONS
GCVM96 / ACVM96 Heating Speed Charts
GCVM960604CX / ACVM960604CX
Rise Range: 20 - 50°F)
Heating
Adjust
Low-Stage
Speed
Tap
CFM (70%) *
Tap
Minus(-)
A
Normal
Plus (+)
Minus(-)
B
Normal
Plus (+)
1,067
Minus(-)
C
Normal
1,040
Plus (+)
1,144
Minus(-)
1,008
D
Normal
1,120
Plus (+)
1,232
GCVM961005DX / ACVM961005DX
Rise Range: 25 - 55°F)
Heating
Adjust
Low-Stage
Speed
Tap
CFM (70%) *
Tap
Minus(-)
1,098
A
Normal
1,220
Plus (+)
1,342
Minus(-)
1,125
B
Normal
1,250
Plus (+)
1,375
Minus(-)
1,170
C
Normal
1,300
Plus (+)
1,430
Minus(-)
1,179
D
Normal
1,310
Plus (+)
1,441
No tes
All furnac es ship as high speed for c ooling. I nstaller must adjust blower s peed as needed.
F or most jobs , about 400 CFM per ton when c ooling is des irable.
Do not operate above .5" w.c. ESP in heating mode. O perating CFM between . 5" and .8" w.c. is tabulated for cooling purposes only.
20
High-Stage
Rise
CFM *
(°F)
792
1,098
880
1,220
968
1,342
873
1,206
970
1,340
1,474
936
1,314
1,460
1,606
1,431
1,590
1,749
High-Stage
Rise
CFM *
(°F)
1,557
1,730
1,903
1,593
1,770
1,947
1,656
1,840
2,024
1,683
1,870
2,057
GCVM960805DX / ACVM960805DX
Heating
Adjust
Speed
Tap
Tap
48
Minus(-)
A
44
Normal
40
Plus (+)
44
Minus(-)
40
B
Normal
36
Plus (+)
40
Minus(-)
C
36
Normal
33
Plus (+)
37
Minus(-)
D
33
Normal
30
Plus (+)
56
51
46
55
49
45
53
48
43
52
47
43
Rise Range: 20 - 50°F)
Low-Stage
High-Stage
CFM (70%) *
CFM *
999
1,440
1,110
1,600
1,221
1,760
1,080
1,539
1,200
1,710
1,320
1,881
1,143
1,620
1,270
1,800
1,397
1,980
1,197
1,719
1,330
1,910
1,463
2,101
Rise
(°F)
49
44
40
46
41
38
44
39
36
41
37
34

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents