3.1 DESCRIPTION
3 HARDWARE
b) JX REMOVED AND ONE OF THE TWO INTERNAL CONTACTS SET AS NORMALLY CLOSED:
It is possible to change by hardware the contact configuration from normally open to normally closed (see the first point of
3
this document).
c) OUT1 NORMALLY CLOSED AND OUT2 NORMALLY OPEN:
The hardware configuration corresponds to OUT1 NC and OUT2 NO. To operate with this hardware configuration it is
necessary to configure by software the OUT1 as NOT ASSIGNED, so it never change its state and remains closed, and
OUT2 as required by the application (output configuration is only available in models option 1 and 2).
d) OUT1 NORMALLY OPEN AND OUT2 NORMALLY CLOSED:
The hardware configuration corresponds to OUT1 NO and OUT2 NC. To operate with this hardware configuration it is
necessary to configure by software the OUT2 as NOT ASSIGNED, so it never change its state and remains closed, and
OUT1 as required by the application (output configuration is only available in models option 1 and 2).
3-12
MIFII Digital Feeder Relay
GEK-106237P