6 I/0 CONFIGURATION

6.2OUTPUTS AND LEDS CONFIGURATION (FOR OPTIONS 1 AND 2)

MIFII incorporates 6 outputs and 6 LED indicators. 4 of the outputs and LED indicators are user configurable, and can only
be programmed using EnerVista MII SETUP software (SETPOINT – RELAY CONFIGURATION). The first two LEDs are
fixed for READY (System ready) and TRIP. The fixed outputs are programmed for ALARM (System alarm) and TRIP.
The TRIP LED activates when the TRIP contact closes.
The READY LED turns on when all the following conditions are fulfilled:
The relay status is READY
At least one of the protection functions of the active table is enabled
The trip of at least one of the enabled functions is also enabled.
The default configuration for outputs is as follows:
OUTPUT
1
2
3
4
The default LED configuration is as follows:
LED
1
2
3
4
GEK-106237P
6.2 OUTPUTS AND LEDS CONFIGURATION (FOR OPTIONS 1 AND 2)
CONFIGURATION
MODELS WITHOUT
MODELS WITH RECLOSER
RECLOSER
Phase trip
Close breaker
Ground trip
Phase trip
50 trip
Ground trip
49 Alarm
50 trip
CONFIGURATION
Phase trip
Ground trip
50 Trip
Pickup
MIFII Digital Feeder Relay

6.2.1 DESCRIPTION OF OUTPUTS AND LEDS

MEMORY
No
No
No
No
MEMORY
Yes
Yes
Yes
No
6