2 PRODUCT DESCRIPTION
A five-button keypad allows access to MIFII relay information and settings changes. Measurement data (actual values), five
last trip information (fault reports) and settings are shown on the 16x2 character LCD display.
The keypad includes the functionality to modify the contrast of the display (refer to Chapter 8 for details).
The event list, oscillography, I/O and logic configuration can be accessed only from the EnerVista MII SETUP program.
The front RS232 and the rear RS485 port provide interface with the relay. All serial ports of the standard model use the
Modbus® RTU protocol and may be connected to system computers with baud rates from 300 to 19200 bps. Up to 32 MIFII
relays can be connected (daisy-chained) on the same communication circuit. Each relay must be assigned a different
Modbus Address (using a setting) if multiple relays are connected on the same circuit.
A special model with IEC60870-5-103 protocol is also available, which uses the rear port with 9600 and 19200 bps baud
rates.
MIFII units are supplied together with EnerVista MII SETUP software, a Windows
communication with the relay for data viewing and retrieval, as well as oscillography, I/O configuration and logical
configuration (in models where these features are available).
GEK-106237P
MIFII Digital Feeder Relay
2.14 USER INTERFACE

2.14.2 KEYPAD AND DISPLAY

2.14.3 COMMUNICATION PORTS

2.14.4 SOFTWARE

®
based software that allows