9.16 GROUND TOC ELEMENT (51G)
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 31.94 and 36.02 sec.
Apply 5 times the pickup current and the relay should trip between 2.31 and 2.60 sec.
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 122.17 and 137.77 sec.
Apply 5 times the pickup current and the relay should trip between 31.35 and 35.36 sec.
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 1.38 and 1.56 sec.
Apply 5 times the pickup current and the relay should trip between 0.53 and 0.60 sec.
Set the relay as follows:
9
Apply 0.9 times the pickup current at phase C and the relay should not trip.
Apply 2 times the pickup current and the relay should trip between 43.3 and 47.8 sec.
Apply 5 times the pickup current and the relay should trip between 23.4 and 25.9 sec.
9-22
51G SETTINGS GROUP
Curve
Time Dial
51G SETTINGS GROUP
Curve
Time Dial
51G SETTINGS GROUP
Curve
Time Dial
51G SETTINGS GROUP
Curve
Time Dial
MIFII Digital Feeder Relay
9.16.9 IAC EXTREMELY INVERSE CURVE
EXTREMELY INVERSE
10
9.16.10 IAC INVERSE LONG CURVE
VERY INVERSE
10
9.16.11 IAC INVERSE SHORT CURVE
EXTREMELY INVERSE
10
EPTAR C
1
9 RELAY COMMISSIONING
9.16.12 EPTAR C CURVE
GEK-106237P