AHRI* capacity ratings
CAPACITY
UNIT
30RAP
Tons
kW
010
10.5
36.8
015
14.0
49.2
018
16.1
56.6
020
18.8
66.1
025
23.4
82.3
030
27.6
97.1
035
34.4
121.0
040
38.9
136.8
045
43.1
151.6
050
47.3
166.3
055
51.8
182.2
060
56.0
196.9
LEGEND
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
IPLV — Integrated Part Load Value
COMPRESSOR
FAN
POWER INPUT
POWER
(kW)
(kW)
10.7
1.2
15.6
1.3
15.6
3.0
19.1
2.9
24.5
2.8
30.9
2.7
35.9
3.8
42.3
3.8
48.6
3.4
53.1
3.8
56.4
5.3
60.8
5.3
TOTAL
FULL LOAD
POWER
(kW)
EER
COP
EER
12.0
10.5
3.1
14.5
16.8
10.0
2.9
13.1
18.6
10.4
3.0
14.3
21.9
10.3
3.0
14.0
27.4
10.3
3.0
15.0
33.6
9.9
2.9
14.7
39.7
10.4
3.0
15.2
46.1
10.1
3.0
15.2
52.0
10.0
2.9
15.3
57.0
10.0
2.9
14.5
61.7
10.1
3.0
14.5
66.2
10.2
3.0
14.3
* Air Conditioning, Heating, and Refrigeration Institute.
NOTE: Based on AHRI-550/590 standard rating conditions. Ratings are for
standard chillers only. Ratings do not include options.
COOLER FLOW
IPLV
RATE
COP
GPM
L/s
4.2
25.1
1.6
3.8
33.6
2.1
4.2
38.6
2.4
4.1
45.2
2.9
4.4
56.3
3.6
4.3
66.3
4.2
4.5
82.5
5.2
4.5
93.4
5.9
4.5
103.4
6.5
4.2
113.5
7.2
4.2
124.2
7.8
4.2
134.4
8.5
COOLER
WATER
PRESSURE
DROP
Ft wg
kPa
13.7
40.9
15.7
46.8
15.6
46.5
14.2
42.4
17.8
53.1
20.9
62.3
13.2
39.4
13.8
41.2
15.3
45.6
19.1
57.0
17.6
52.5
20.5
61.2