Major System Components And Operation Data; Direct-Drive Twin-Screw Compressor With Variable Capacity Slide Valve; Pressure Vessels - Carrier AquaForce PUREtec 30XBEZE 200 Installation, Operation And Maintenance Instructions

Air-cooled screw chillers
Table of Contents

Advertisement

11 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA

11.1 - Direct-drive twin-screw compressor with
variable capacity slide valve
- 30XB(E/P)ZE units use 06T geared twin-screw compressors
equipped with a variable capacity slide valve for continuous
control between 30% and 100% of full load.
- Nominal capacities range from 100 to 600. The ten models
used in the 30XBEZE & 30XBPZE range are economised.
11.1.1 - Oil filter
The 06T screw compressor has an independent oil filter attached 
to the oil separator. This filter is field replaceable.
11.1.2 - Refrigerant
The 30XBEZE & 30XBPZE range units must operate with
R1234ze(E) refrigerant.
11.1.3 - Lubricant
The 06T screw compressor is approved for use with the following
lubricant (Carrier specification PP47-38).
CAUTION : Too much oil in the circuit can cause the unit to
malfunction.
NOTE : Never use oils which have been exposed to air.
11.1.4 - Oil supply solenoid valve
An oil supply solenoid valve is installed on the oil return line as
standard to isolate the compressor from oil flow when the compressor 
is not operating. The oil solenoid valve is field replaceable.
11.1.5 - Suction and economizer screens
To increase the reliability of the compressor, a screen has been
incorporated as a standard feature into suction and economizer
inlets of the compressor.
11.1.6 - Capacity control system
The 06T screw compressor has an unloading system that is
standard on all compressors. This unloading system consists of
slide valve that permits changing the length of the screw used for
the refrigerant compression. This valve is controlled by the action
of a piston controlled by two solenoid valves on the oil return line.

11.2 - Pressure vessels

General
Monitoring  during  operation,  re-qualification,  re-testing  and  re-
testing dispensation:
- Follow the regulations on monitoring pressurised equipment.
- It is normally required that the user or operator sets up and
maintains a monitoring and maintenance file.
- If there are no regulations or to complement them follow the
control programmes of EN 378.
- If they exist follow local professional recommendations.
- Regularly inspect the condition of the coating (paint) to detect
blistering resulting from corrosion. To do this, check a non-
insulated section of the container or the rust formation at the
insulation joints.
- Regularly check for possible presence of impurities (e.g.
silicon grains) in the heat exchange fluids. These impurities 
maybe the cause of the wear or corrosion by puncture.
- Filter the heat exchange fluid check and carry out internal 
inspections as described in EN 378.
- In case of re-testing please refer to the maximum operating
pressure given on the unit nameplate.
- The reports of periodical checks by the user or operator must
be included in the supervision and maintenance file.
50
Repair
Any repair or modification, including the replacement of moving parts:
- Must  follow  local  regulations  and  be  made  by  qualified 
operators  and  in  accordance  with  qualified  procedures, 
including changing the heat exchanger tubes.
- Must be made in accordance with the instructions of the
original manufacturer. Repair and modification that
necessitate permanent assembly (soldering, welding,
expanding etc.) must be made using the correct proce-dures
and by qualified operators.
- An indication of any modification or repair must be shown in 
the monitoring and maintenance file.
- Never attempt to repair or modify a plate heat exchanger.
Recycling
The unit is wholly or partly recyclable. After use it contains
refrigerant vapours and oil residue. It is coated by paint.
Operating life
This unit is designed for:
- Prolonged storage of 15 years under nitrogen charge with a
temperature difference of 20 K per day.
- 10,000 cycles (start-ups) during the whole lifetime.
Corrosion allowances:
Gas side: 0 mm
Heat exchange fluid side: 1 mm for tubular plates in lightly alloyed 
steels, 0 mm for stainless steel plates or plates with copper-nickel
or stainless steel protection.
Water-box : 1 mm
Parts painted : 0 mm
If any part of the piece (with 0mm of acceptable corrosion) shows
corrosion, change the piece.
Unit PED classifications
The  unit  PED  classification  depending  are  presented  in  the 
following tables. The unit classification is driven by the the highest 
PED class equipment.
30XB(E/P)ZE
200 230 250 300 350 400 450 500 550
Standard unit
PED Category
III
III
30XB(E/P)ZE
600 630 700 750 900 950 1050 1150 1200
Standard unit
PED Category
IV
IV
III
III
III
III
III
III
IV
IV
IV
IV
IV
IV
IV
IV

Advertisement

Table of Contents
loading

Table of Contents