Trane Voyager Commercial Installation & Operation Manual page 74

Commercial 27.5 to 50 ton 60 hz, 22.9 to 41.7 ton 50 hz cv or vav rooftop air conditioners with reliatel controls, r-410a refrigerant
Hide thumbs Also See for Voyager Commercial:
Table of Contents

Advertisement

Startup
Table 28. Test Mode States for VAV Units with Modulating Dehumidification
TEST
STEP
MODE
1
IGV TEST OPEN
IGV TEST
2
CLOSED
CLOSED
3
MIN VENT
CONTROL
ECON TEST
4
OPEN
CONTROL
5
COOL
STAGE 1
CONTROL
6
COOL
STAGE 2
CONTROL
7
COOL
STAGE 3
CONTROL
8
REHEAT
CONTROL
9
HEAT
STAGE 1
10
HEAT
STAGE 2
11
RESET
Table 29. Test Mode States for CV Units with Modulating Dehumidification
TEST
STEP
MODE
FAN
1
MIN VENT
ON
ECON TEST
2
ON
OPEN
3
COOL
ON
STAGE 1
4
COOL
ON
STAGE 2
5
COOL
ON
STAGE 3
6
REHEAT
ON
7
HEAT
ON
STAGE 1
8
HEAT
ON
STAGE 2
9
RESET
74
IGV
FAN
ECON
OPEN
OFF
CLOSED
OFF
CLOSED
IN
ON
MIN
IN
ON
OPEN
IN
ON
MIN
IN
ON
MIN
IN
ON
MIN
IN
ON
MIN
OPEN
ON
CLOSED
OPEN
ON
CLOSED
ECON
COMP 1
COMP 2
MIN
OFF
OPEN3
OFF
MIN
ON1
MIN
OFF
MIN
ON1, 2
MIN
ON1
MIN
OFF
MIN
OFF
COMP 1
COMP 2
HEAT 1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
,
ON
ON
ON
ON
OFF
OFF
OFF
OFF
HEAT 1 HEAT 2 Pumpout Cool Valve
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON1
OFF
OFF
ON1, 2
OFF
OFF
ON1
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
HEAT 2
Pumpout
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
ON
Reheat
ON
100%
ON
100%
ON
100%
ON
100%
ON
100%
OFF
50%
ON
100%
ON
100%
Cool
Reheat
Valve
Valve
100%
0%
100%
0%
100%
0%
100%
0%
100%
0%
100%
0%
100%
0%
50%
50%
100%
0%
100%
0%
Valve
0%
0%
0%
0%
0%
50%
0%
0%
RT-SVX34C-EN