7. Pressure test the supply line before connecting it to the unit to prevent possible gas valve

Connecting the Gas Supply Line to the Furnace Gas Train

Follow the steps below to complete the installation between the supply gas line and the furnace.
Refer to
1. Connect the supply gas piping using a "ground-joint" type union to the furnace gas train and
2. Provide adequate support for the field installed gas piping to avoid stressing the gas train and
3. Adjust the inlet supply gas pressure to the recommended 6" for natural gas or 11" w.c. for LP gas.
Table 16. Sizing Natural Gas Pipe Mains and Branches
Gas Supply
Pipe Run (ft)
10
20
30
40
50
60
70
80
90
100
125
150
175
200
Notes:
1. If more than one unit is served by the same main gas supply, consider the total gas input
2. Obtain the Specific Gravity and BTU/Cu.Ft. from the gas company.
3. The following example demonstrates the considerations necessary when determining the
Example: A 40' pipe run is needed to connect a unit with a 500 MBH furnace to a natural gas
Cu.Ft/Hour = Furnace MBH Input
Gas BTU/Cu.Ft. X Multiplier
Cu.Ft/Hour = 500
*Table is based on a specific gravity of 0.60. Use
RT-SVX34C-EN
damage and the unsafe operating conditions that will result.
Note: Do not rely on gas train shutoff valves to isolate the unit while conducting gas pressure/
leak test. These valves are not designed to withstand pressures in excess of 14" w.c. or
0.5 psig.
Figure 33, p. 52
for the Gas Train configuration.
check for leaks.
controls.
Gas Input (Cubic Feet/Hour)*
1-1/4"
1-1/2"
Pipe
Pipe
1050
1600
730
1100
590
890
500
760
440
670
400
610
370
560
350
530
320
490
305
460
275
410
250
380
225
350
210
320
(cubic feet/hr.) and the total length when determining the appropriate gas pipe size.
actual pipe size.
supply having a rating of 1,000 BTU/Cu.Ft. and a specific gravity of 0.60
Table 17, p. 52
Table 16
indicates that a 1-1/4" pipe is required.
local gas supply.
2-1/2"
3"
2" Pipe
Pipe
Pipe
3050
4800
8500
2100
3300
5900
1650
2700
4700
1450
2300
4100
1270
2000
3600
1150
1850
3250
1050
1700
3000
990
1600
2800
930
1500
2600
870
1400
2500
780
1250
2200
710
1130
2000
650
1050
1850
610
980
1700
Table 17, p. 52
or the specific gravity of the
Installation Piping
4"
Pipe
17500
12000
9700
8300
7400
6800
6200
5800
5400
5100
4500
4100
3800
3500
51