Trane Voyager Commercial Installation & Operation Manual page 45

Commercial 27.5 to 50 ton 60 hz, 22.9 to 41.7 ton 50 hz cv or vav rooftop air conditioners with reliatel controls, r-410a refrigerant
Hide thumbs Also See for Voyager Commercial:
Table of Contents

Advertisement

The following Constant Volume or Variable Air Volume controls are available
from the factory for field installation.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and timed override with override cancellation.
It is used with a Trane Integrated Comfort
Figure 27. Remote Zone Sensor (BAYSENS073*)
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability and timed override with override
cancellation. It is used with a Trane Integrated Comfort
Figure 28. Remote Zone Sensor (BAYSENS074*)
Remote Zone Sensor (BAYSENS077*)
This electronic sensor can be used with BAYSENS106*, 108*, 110*, 119*, or 021* Remote Panels.
When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded
Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
Remote Panel with NSB (BAYSENS119*)
This 7 day programmable sensor features four periods for Occupied\Unoccupied programming per
day. Either one or all four periods can be programmed. If the power is interrupted, the program is
retained in permanent memory. If power is off longer than 2 hours, only the clock and day may have
to be reset.
The front panel allows selection of Occupied/Unoccupied periods with two temperature inputs
(Cooling Supply Air Temperature and Heating Warm-up temperature) per occupied period. The
occupied supply air cooling setpoint ranges between 40o and 80o Fahrenheit. The warm-up
setpoint ranges between 50 and 90 degrees Fahrenheit with a 2 degrees deadband. The
Unoccupied cooling setpoint ranges between 45 and 98 degrees Fahrenheit. The unoccupied
heating setpoint ranges between 43 and 96 degrees Fahrenheit.
Note: In modulating gas heat units, the supply air heating setpoint is the active setpoint with a
RT-SVX34C-EN
BAYSENS119* and must be set for the heater to function properly. The modulating furnace
will not react to the Discharge Heating Setpoint on the NSB.
TM
building management system.
TM
building management system.
Installation Electrical
45