DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual
④ Set the suspension bolt. (Use M10 size suspension bolts)
⑤ Adjust the distance between the unit and the ceiling slab beforehand (See Fig.43). Fix the hanger bracket
to the suspension bolt.
WARNING!
● Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. Readjust the
hanger bracket when it is outside the arrowed position. (See Fig.45)
● Suspension bolt stays inside the cap of the indoor unit .Never remove the cap. Lift the unit and slide the
hanger bracket in the way that the holes on it will match with the corresponding bolts. (See Fig.46)
● Screw tightly both hanger brackets setting bolts (M10.) (See Fig.44)
● Screw tightly both hanger bracket fixing bolts (M6) to prevent the movement of the indoor unit. (See
Fig.44)
● Adjust the height of the unit to incline slightly the rear side of the drain pipe so as to optimize the
drainage.
CAUTION
Adjust the height by turning the unit with a spanner. Insert the spanner from the hanger bracket opening.
(See Fig.48)
Hanging and Mounting
It is possible to carry out the installation by using inward facing hanger brackets without moving the
brackets from the indoor unit. (See Fig.47)