Start-Up Procedures

Boiler Control Display

Standby Mode

After the boiler is turned on, the control panel
will display STANDBY mode as shown in the
figure above.
This is the standard mode for the PRESTIGE.
The control automatically returns to this mode
after 20 minutes if no keys have been pressed
on the display. Any parameters that were mod-
ified are then enabled.
The first character shows (on left side of dis-
play) the current status of the boiler depending
on the condition of both the boiler and the
burner. The last 3 characters indicate the start
temperature.
If the burner is blocked due to a "soft" lockout,
the display alternates between a 9 followed by
the boiler outlet temperature and a "b" with a
two digit error code.
TO T E M P O R A R I LY PLACE THE BURN-
ER INTO HIGH FIRE T E S T M O D E : press
the MODE button until "
Then press and hold both the MODE and "+"
button simultaneously until the first digit flash-
es "H".
While in the test mode:
-
high limit will function
-
boiler circulator will function
-
domestic circulator will not function
-
the test mode will time out in approxi-
mately 10 minutes
StbY
" is displayed.
TO TEMPORARILY PLACE THE BURN-
ER INTO LOW FIRE TEST MODE: press
the MODE button until "
Then press and hold both the mode and "-" but-
ton simultaneously until the first digit flashes
"L".
Press and hold the "+" and "-" button simulta-
neously to deactivate the high or low fire test
mode. While in the "
NOTICE
If the "+" button is held in the CH sys-
tem (parameter 2) will be turned OFF
and the display will show "
Press and hold the "+" button to turn the
CH system back ON, the display will
show "c" followed by CH set point tem-
perature (parameter 4) or CH target
temperature. If the "-" button is held in
while in the "
system (parameter 3) will be turned OFF
and the display will show "
Press and hold "-" button to turn the
domestic system back ON, the display
will show "d" followed by domestic set
point temperature (parameter 1)
43
StbY
" is displayed.
StbY
" mode,
C O F F
StbY
" mode domestic
C O F F
".
".