Installation Positions; Horizontal Applications & Considerations; General; Drain Trap And Lines - Goodman GMV9 Installation Instructions Manual

Two-stage gas-fired warm air furnace
Table of Contents

Advertisement

5.3.6 Special Conditions Created by Mechanical Exhausting or Fire-
places:
Operation of exhaust fans, ventilation systems, clothes dryers, or fireplaces
may create conditions requiring special attention to avoid unsatisfac-
tory operation of installed gas utilization equipment. Air from Inside
Building. See 5.3.3-a.
VI. INST
VI. INST
VI. INST
VI. INST
VI. INSTALL
ALLA A A A A TI
ALL
ALL
ALL
This furnace may be installed in an upright position or horizontal on
either the left or right side panel. Do not install this furnace on its
back. For upright upflow furnaces, return air ductwork may be at-
tached to the side panel(s) and/or basepan. For horizontal upflow
furnaces, return air ductwork must be attached to the basepan. For
both upright or horizontal counterflow furnaces, return ductwork must
be attached to the basepan (top end of the blower compartment).
NOTE: Ductwork must never be attached to the back of the fur-
nace. Contact your distributor for proper airflow requirements and
number of required ductwork connections. Refer to "Recommended
Installation Positions" figure for appropriate installation positions,
ductwork connections, and resulting airflow arrangements.
VII. HO
VII. HO
RIZO
RIZO
NT
NT
AL APPLI
AL APPLIC C C C C A A A A A TI
AL APPLI
VII. HORIZO
VII. HO
VII. HO
RIZONT
RIZO
NTAL APPLI
NT
AL APPLI
G
ENERAL
Horizontal applications, in particular, may dictate many of the
installation's specifics such as airflow direction, ductwork connec-
tions, flue and combustion air pipe connections, etc. The basic ap-
plication of this furnace as a horizontal furnace differs only slightly
from an upright installation. When installing a furnace horizontally,
additional consideration must be given to the following:
ALTERN ATE VENT/FLUE
AND CO M BUSTIO N AIR
IN TAKE LO CATIO NS
GA S LINE W ITH
DR IP LEG (3" M INIM U M)
DRAIN PAN
FURNACE M UST BE SU PPOR TE D
AT BO TH EN DS A ND MIDDLE
Horizontal Furnace
D
T
L
RAIN
RAP AND
INES
In horizontal applications the condensate drain trap is secured to
the furnace side panel, suspending it below the furnace. A mini-
mum clearance of 4 3/4 inches below the furnace must be provided
for the drain trap. Additionally, the appropriate downward piping
slope must be maintained from the drain trap to the drain location.
Refer to Section X, Condensate Drain Trap and Lines for further
details. If the drain trap and drain line will be exposed to tempera-
tures near or below freezing, adequate measures must be taken to
prevent condensate from freezing.
L
EVELING
Leveling ensures proper condensate drainage from the heat ex-
changer and induced draft blower. For proper flue pipe drainage,
the furnace must be level lengthwise from end to end. The furnace
should also be level from back to front or have a slight tilt with the
TI
TI
TIO O O O O N POSITI
TI
N POSITIO O O O O NS
N POSITI
N POSITI
N POSITI
NS
NS
NS
NS
TI
TIO O O O O NS & CO
TI
NS & CO
NS & CO
NSID
NSID
ERA
ERA
TI
NS & CO
NS & CONSID
NSID
NSIDERA
ERATI
ERA
FUR NACE MU ST BE LE VE L
FRO M EN D TO EN D
FURN ACE M UST BE LEV EL
O R SLIG HTLY TILTED F ORW AR D
W ITH T HE D OO RS 0" - 3/4"
BELO W THE BACK PAN EL
4 3/4" M IN IM UM
DRA IN TR AP
CLEARANC E
D RAIN LINE W ITH 1/4" PER FOO T
D OW NW ARD SLOPE
36" MINIM UM SERVIC E
CLE ARANCE REQ UIR ED
access doors downhill (approximately 3/4 inches) from the back
panel. The slight tilt allows the heat exchanger condensate, gener-
ated in the recuperator coil, to flow forward to the recuperator coil
front cover.
A
V
LTERNATE
ENT
In horizontal installations provisions for alternate flue and combus-
tion air piping are available for upflow furnaces with left discharge
and counterflow furnaces with right air discharge. This configura-
tion allows the flue and combustion air piping to be run vertically
through the side of the furnace. Refer to the "Recommended Instal-
lation Positions" figure for further detail. The standard piping con-
nections may also be used in these positions. Refer to Section IX,
Vent/Flue Pipe and Combustion Air Pipe for details concerning the
conversion to the alternate vent/flue and combustion air connec-
tions.
TIO O O O O NS
TI
TI
NS
NS
TI
NS
NS
Recommended Installation Positions
NOTE: Alternate "vertical" piping connections can not be used when
an upflow furnace is installed with supply air discharging to the right,
or when a counterflow furnace is installed with supply air discharging
to the left. In either case, use the standard flue and combustion air
piping connections.
A
E
LTERNATE
LECTRICAL AND
This furnace has provisions allowing for electrical and gas line con-
nections through either side panel. In horizontal applications the
connections can be made either through the "top" or "bottom" of the
furnace.
D
P
RAIN
AN
A drain pan must be provided if the furnace is installed above a
conditioned area. The drain pan must cover the entire area under
the furnace (and air conditioning coil if applicable).
F
P
REEZE
ROTECTION
Refer to Section VII, Horizontal Applications and Conditions - Drain
Trap and Lines.
F
S
URNACE
USPENSION
If the furnace is installed in a crawl space it must be suspended
from the floor joist or supported by a concrete pad. Never install the
furnace on the ground or allow it to be exposed to water. Refer to
11
/F
C
A
LUE AND
OMBUSTION
AIR
ALTERNATE FLUE AND
DISCHARGE
COMBUSTION AIR PIPE
LOCATIONS
Side
Side
Return
Return
Duct
Duct
Connection
Connection
Bottom
Return
Duct
Connection
UPFLOW
UPRIGHT
ALTERNATE FLUE AND
COMBUSTION AIR PIPE
LOCATIONS
Bottom
Return
AIR
Duct
DISCHARGE
Connection
UPFLOW HORIZONTAL
LEFT AIR DISCHARGE
Bottom
Return
AIR
Duct
DISCHARGE
Connection
UPFLOW HORIZONTAL
RIGHT AIR DISCHARGE
G
L
C
AS
INE
ONNECTIONS
C
IR
ONNECTIONS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gcv9

Table of Contents