Hitachi SJ700B SERIES Quick Reference Manual page 50

Inverter
Hide thumbs Also See for SJ700B SERIES:
Table of Contents

Advertisement

Code
Function name
b001
Selection of restart mode
Allowable under-voltage power
b002
failure time
b003
Retry wait time before motor restart 0.3 to 100.0 (s)
Instantaneous power
b004
failure/under-voltage trip alarm
enable
Number of restarts on power
b005
failure/under-voltage trip events
b006
Phase loss detection enable
b007
Restart frequency threshold
b008
Selection of retry after tripping
b009
Selection of retry after undervoltage 00 (16 times), 01 (unlimited)
Selection of retry count after
b010
overvoltage or overcurrent
b011
Retry wait time after tripping
Electronic thermal setting
b012
(calculated within the inverter from
current output)
Electronic thermal setting
b212
(calculated within the inverter from
current output), 2nd motor
Electronic thermal setting
b312
(calculated within the inverter from
current output), 3rd motor
b013
Electronic thermal characteristic
Electronic thermal characteristic, 2nd
b213
motor
Electronic thermal characteristic, 3rd
b313
motor
Free setting, electronic thermal
b015
frequency (1)
Free setting, electronic thermal
b016
current (1)
Free setting, electronic thermal
b017
frequency (2)
Free setting, electronic thermal
b018
current (2)
Free setting, electronic thermal
b019
frequency (3)
Free setting, electronic thermal
b020
current (3)
b021
Overload restriction operation mode
b022
Overload restriction setting
Deceleration rate at overload
b023
restriction
Overload restriction operation mode
b024
(2)
b025
Overload restriction setting (2)
Deceleration rate at overload restriction
b026
(2)
b027
Overcurrent suppression enable
Active frequency matching, scan
b028
start frequency
Active frequency matching,
b029
scan-time constant
Active frequency matching, restart
b030
frequency select
b031
Software lock mode selection
Monitored data or setting
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)
0.3 to 25.0 (s)
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating
to stop)
00 (16 times), 01 (unlimited)
00 (disabling), 01 (enabling)
0.00 to 99.99, 100.0 to 400.0 (Hz)
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)
1 to 3 (times)
0.3 to 100.0 (s)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free
setting)
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free
setting)
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free
setting)
0. to 400. (Hz)
0.0 to rated current (A)
0. to 400. (Hz)
0.0 to rated current (A)
0. to 400. (Hz)
0.0 to rated current (A)
00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
constant speed
(increasing the speed during regeneration))
0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
constant speed
(increasing the speed during regeneration))
0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling)
0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set
frequency)
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling
change of data other than "b031" and frequency settings when SFT is on), 02
(disabling change of data other than "b031"), 03 (disabling change of data
other than "b031" and frequency settings), 10 (enabling data changes during
operation)
4 - 7
Chapter 4 List of Data Settings
Default
_F/_FF
_FUF
00
1.0
1.0
00
00
00
0.00
00
00
3
1.0
Rated current of inverter
Rated current of inverter
Rated current of inverter
01
01
01
0.
0.0
0.
0.0
0.
0.0
01
Rated current of inverter x
1.20
1.00
01
Rated current of inverter x
1.20
1.00
01
Rated current of inverter
0.50
00
01
Setting
Change
during
during
operation
operation
(allowed or
(allowed or
not)
not)