-- ±15 volts for 120V models and ±16 volts for 240V models. Perform the
calibration sequence multiple times if a larger adjustment is required.
*
For 240V models, enter even voltages only.
Click OK to accept the value. The application then displays a confirmation
message, as illustrated below:
Click the Yes button to start the calibration process. The application displays
a timer in the calibration window to indicate progress.
Click the No button to cancel the calibration process. No changes are made
to the PowerWatch logger.
Click the CANCEL button at anytime to stop the calibration. The application
then displays the following dialog:
Cancelling the calibration process restores the previous calibration settings of
the PowerWatch.