Venting - Weil-McLain CGi Series 3 Installation And Maintenance Manual

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
14
3a
3b
Table 3
Vent
connector
diameter
Figure 7
Chimney
draft
venting
Venting - general information
CGi venting methods - Chimney draft or Direct exhaust
Chimney draft
venting
Chimney d raft venting
uses
the
natural
draft p
rovided
by a vertical
vent
o
r
chimney. Category
I
appliance (no
n-
positive
vent
static pressure and vent gas
temperature
that avoids excessive condensate
production
tn
ven
t).
See
Section
3b.
C
himney draft
installations use:
Direct
exhaust
-
vertical
or
sidewall
Direct exhaust venting uses
inside
combustion air with
no combustio
n air connector
piping.
All CGi
flue
gas
vents are
pressurized,
requiring careful
sealin~
of all
joints. Category
Ill
appliance (positive vent static
pres-
sure and vent gas teml?erature that avoids excessive
condensate
production m
vent). See
pages
15-19.
1. Vent
connecto
r
(single
or d
ouble wall)
sized
to
eliminate positive pressure
in vent
system.
Diameter
increases immediately
at
boiler.
Direct
exhaust
installations
use:
1.
V ent
pipe
specified in this manual
2. Double
wall metal vent
(B-vent)
or
chinmey
with
liner approved
by the
National Fuel
Gas
Code, ANSI
Z223.1-latest edition,
o
rin CanadaBI49.1
o
r
Bl49.2
Installation Cod
e.
2.
V ent termination
through
outside
wall,
roof or
tm-
used chimney.
Tigh
t chimney areas
will
make
vent
joint
constructio
n
very
difficult.
Venting - chimney draft venting
Boiler
''0'
1
Minimum
model
vent connector
number
diameter
CG;-25 & CGi-3
4"
CGi-4 to CGi-8
5"
Il-l.
--
-
Chimney
I&WARNING
l
Inspect existing chim ney before installing boiler. Failure to
clean
or rel?lace
perforated
pipe
o
r
lining will
cause
severe
personal
inJury
o
r
death.
V ent
sizing
given in
Table
3
is only
a
general
guideline. The
vent
connector
and chimney m
ust
be designed,
sized and
constructed in compliance
with all
applicable
codes.
Failure
to
correctly
siu
and
install
the vent
system could
result
in
severe
personal
injury,
death
o
r
substantial p
roperty
damage.
1.
Use
do
uble
wall
metal vent
(B-vent)
or
chimney
with
liner
as
required
by
the
National Fuel Gas Code, ANSI Z223.1-latest
edition, or in
Canada,
B149.1
or B149.2
Installatio
n
Code.
2.
To
prevent
downdrafts, chimney
should
extend
at least
3
feet
above the highest po int where
it
passes through
a
roof
and
at
least 2
feet
higher
than
any portion of
a
building
within
a
horizontal distance of
I
0
feet.
3. To
vent with another appliance, see
Natio
nal Fuel Gas
Code,
ANSI
Z223.1-latest
edition
o
r in Canada B149.2 or B149.2
Installation Code
4.
Do not
connect
breeching
to
any
portion
of a mechanical
draft
system that can
operate
under
positive
pressure.
5.
Maintain minimwn
2" clearance
from combustible materials
to vent
pipe.
6.
Do
not
use
chimney
with an open
fireplace.
7.
Make
horizontal runs
as
short
as
possible. Long runs
can
cause
condensation.
8. When longer
runs
are
used,
support pipe
with
appropriate
hangers.
9. To prevent
blockage,
do
not vent
into bo
ttom
of chimney.
10.
V ent pipe must not go beyond inside wall of
chimney.
11.
Vent passing
through
floors
o
r ceilings must be
firesto pped.
12.
See Figure
7
and Table
3
to
connect
boiler
to
venting
sys-
tem.
Part Number 550-142-780/0712