Section One: General Information - Fire-Lite The Sensiscan 200 Installation, Operation, And Programming Manual

Fire alarm control panel
Hide thumbs Also See for The Sensiscan 200:
Table of Contents

Advertisement

Introduction
The Sensiscan 200 is an expandable multi-zone Fire Alarm Control Panel (FACP) based on a modular design
for maximum flexibility. The heart of the system is the Central Processor Unit (CPU) module which monitors and
directs the actions of all other modules in the system. Up to two other modules may be installed in various
configurations. Internal communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the BE-200 Basic Equipment package. This module provides two Style Z and/
or Style Y Notification Appliance Circuits, Form-C alarm and trouble contacts, Remote Station alarm and trouble
outputs, and a Municipal Master Box output.
An initiating circuit module (IZ-4F or IZ-8F) and a CAB-200 cabinet must be added to make the basic system
functional.
The basic system can be expanded using one or more of the following optional modules or boards:
• IZ-8F Initiating Zone Module
• IZ-4F Initiating Zone Module
• IZ-4AF Initiating Zone Module
• IZE-AF Initiating Zone Expander
• IC-4F Indicating Circuit Module
• ICR-4LF Combination Output Module
• ICE-4F Indicating Circuit Expander
System expansion must comply with:
• The physical limitations of the cabinet configuration.
• The electrical limitations of the system power supply (see Appendix A).
• The capacity of the standby battery (see Appendix A).
Key Features
• Distributed microprocessor electronics.
• Field programmable in nonvolatile memory.
• Manual Disable control for all Notification Appliance Circuits and control relays.
• Alarm verification, with device type discrimination.
• Walk Test, with zone change indication.
• Serial annunciators, including LCD and custom annunciators.
• Multiple hazard release control modules.
• Programmable software timers including positive alarm sequence.
4
Section One:
General Information
S200 15032 Rev C 02/22/96 P/N 15032:C
• AVPS-24F Audio-Visual Power Supply
• CR-4F Control Relay Module
• CR-4LF Control Relay Module
• CRE-4F Control Relay Expander
• TC-2F Time Control Module
• TC-4F Time Control Module
• UDACTF Universal Digital Alarm
Communicator Transmitter