4.4.5 Trouble Condition Response
The control panel, upon detection of one or more trouble conditions, well perform the
following:
Blink the FACP System Trouble LED one second On and one second Off
Blink the FACP Zone Trouble LED one second On and one second Off
Turn on remote annunciator Trouble LED and pulse the piezo sounder
Pulse the FACP piezo sounder one second On and one second Off
Transfer fail-safe Trouble relay
Additional LEDs will turn on or blink according to the specific trouble
✓ NAC Disable LED if NAC has been disabled
✓ Zone Disable LED if a zone has been disabled
✓ NAC Fault LED if a fault is detected on an NAC
✓ Power Trouble LED if an AC, battery or charger fault is detected
✓ AC Power LED will turn off if AC fail or brownout occurs
✓ Alarm Silence LED if Silence button is pressed after an alarm or trouble
✓ Walktest LED if Walktest mode is entered
✓ Zone Maintenance LED if a I
✓ Earth Fault LED if a ground fault occurs
✓ Battery Fault LED if low or no battery condition occurs
✓ Charger Fault LED if a charger trouble occurs
4.4.6 Trouble Condition Restoral
The control panel performs the following upon restoral of all trouble conditions:
Turn off the FACP System Trouble LED
Turn off the FACP Zone Trouble LED
Turn off the remote annunciator Trouble LED and piezo sounder
Turn off the piezo sounder
Transfer the fail-safe Trouble relay
Turn off additional LEDs corresponding to specific troubles
2SHUDWLQJ ,QVWUXFWLRQV