The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the decorative gas appliance
are defi ned by standoffs. The metal ends of the
standoff may NOT be recessed into combustible
construction.
Regency Plateau™ PTO30 Outdoor Gas Fireplace
MINIMUM CLEARANCES TO COMBUSTIBLES
PTO30 Clearance Requirements
Clearance:
A: Back wall
B: Sidewall
C: Ceiling
D: Unit Base
E: Alcove Width PTO30
E: Alcove Width PTO60
F: Alcove Depth
Notes:
A
F
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
Dimension
Measured From:
17" (432mm)
Burner to back wall
17" (432mm)
Burner to sidewall
45" (1143mm)
Burner to Ceiling
1"(25mm)
Unit Base to Combustible
84"(2134mm)
Wall to Wall (Minimum)
100" (2540mm)
Wall to Wall (Minimum)
60" (1524mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
C
B
D
E
Alcove
INSTALLATION
WARNING
Fire hazard is an extreme risk
9