No.
Part name
6
Liquid tank
Wear protective clothing on your hands
as other components may cause injury
etc.
<Disassembling>
1) Stop unit operation and turn off power
supply to unit.
Never open the cabinet while five minutes
after turn off the power supply.
2) Remove Inverter assembly by procedure 2.
3) Recover refrigerant.
4) Remove TL sensor at one pipe of Liquid
tank.
5) Take off pipes to Liquid tank by re-welding.
6) Remove Screws and carry up Liquid tank to
upper side. (Screw M5 2 pcs)
Note : Re-transform pipes of Liquid tank for
<Assembling>
Assembling by contrary procedure of above 6) → 1).
• After completion of the repair work, perform vacuuming of the outdoor unit using the
following procedure.
(Procedure)
Short CN30 on the interface P .C. board on the outdoor unit for which the repair work has
been completed, to open the PMV fully. (Confirm that Bit 1 of SW12 is OFF.)
Note : The PMV opening by using short CN30 returns the PMV to fully closed after
Procedure
CAUTION
WARNING
carry out.
Take care for crashing pipes.
2 minutes.
To continue the fully open status, turn off the power supply of the outdoor unit within
2 minutes after using short CN30.
TL sensor
TL sensor
Screw
Screw
178
Remarks
Welding part
Welding part
Welding part
Welding part
Liquid tank
Liquid tank