Check code
Outdoor 7-segment display
Wired
remote
controller Check code
Auxiliary code
H06
H06
L03
L04
L04
L05
L06
L06
No. of indoor units with
priority
L07
L08
L08
L09
L10
L10
L20
L28
L28
Detected
Check code name
AI-NET
position
central control
remote controller
20
I/F
Low-pressure protective operation
96
Indoor
Duplicated indoor center units
96
I/F
Duplicated outdoor line address
96
I/F
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
96
I/F
Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)
99
Indoor
Group line in individual indoor unit.
99
Indoor
Indoor group / address unset
46
Indoor
Indoor capacity unset
88
I/F
Outdoor capacity unset
98
AI-NET,
Duplicated central control addresses
Indoor
46
I/F
Quantity over of connected outdoor
units
Status
Error detection condition
All stop
Low-pressure Ps detected
operation lower than 0.02MPa.
Corresponding
There are multiple header units
unit only stops.
in a group.
All stop
Line address setup is duplicated
against the outdoor unit in
different refrigerant pipe system.
All stop
Indoor units with priority were
duplicated.
All stop
Indoor units with priority were
duplicated.
Corresponding
At least one indoor unit
unit only stops.
connected to a group existed in
the individual indoor units.
Corresponding
Address was not yet set up.
unit only stops.
Corresponding
Indoor unit capacity was unset.
unit only stops.
All stop
On the I/F P .C. board for service,
jumper line was not cut
according to the model.
All stop
Duplicated central control
addresses
All stop
There were more than four
outdoor units.
Check item (position)
• Check full opening of service valve.
(Discharge gas and liquid side)
• Check outdoor PMV clogging.
• Check SV2 circuit and SV4 circuit error.
• Check low-pressure Ps sensor error.
• Check indoor air filter clogging.
• Check valve open of indoor PMV.
• Check refrigerant pipe clogging.
• Check outdoor fan operation. (In heating mode)
• Check refrigerant shortage.
• Check 4-way valve error. (Reversed error.).
• Check indoor address.
• Check the change of remote controller connection
(Group/individual) after indoor address setup.
• Check line address.
• Check display of indoor unit with priority.
• Check display of indoor unit with priority and outdoor
unit.
• Check indoor address.
• Check indoor address.
Note)
After installation, this code is displayed when the power
is first turned on.
Set up indoor capacity. (DN=11)
Check model setup on outdoor I/F P .C. board A'ssy for
service.
• Check central control address.
• Check network adaptor P .C. board. (In case of AI-NET)
• Check No. of connected outdoor units.
(Max. 4 units per 1 system)
• Check communication line between outdoor units.
• Check outdoor P .C. board (I/F) error.