Toshiba MiNi-SMMS MCY-MAP0501HT Service Manual page 119

Mini-super modular multi system
Hide thumbs Also See for MiNi-SMMS MCY-MAP0501HT:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Wired
remote
controller Check code
Auxiliary code
F23
F23
F24
F24
F29
F31
F31
H01
H01
01: Compressor 1
H02
H02
01: Compressor 1
H03
H03
01: Compressor 1
H04
H04
(*1) All stop only in case of the header unit
Detected
Check code
AI-NET
position
name
central control
remote controller
43
I/F
Ps sensor error
43
I/F
Pd sensor error
12
Indoor
Indoor other
error
1C
I/F
Outdoor
EEPROM error
1F
IPDU
Compressor
breakdown
1d
IPDU
Compressor
error (lock)
17
IPDU
Current
detection circuit
system error
44
I/F
Compressor 1
case thermo
operation
The follower unit continues operation.
Status
Error detection condition
All stop
Output voltage of Ps sensor was zero.
All stop
Output voltage of Pd sensor was zero.
(Sensor Open)
Pd > 4.15MPa during stop of compressor
Corresponding
Indoor P .C. board did not operate normally. • Check indoor P .C. board error (EEPROM error).
unit only stops.
All stop (*1)
Outdoor P .C. board (I/F) did not operate
normally.
All stop
Inverter current detection circuit detected
over-current and stopped.
All stop
Over-current was detected several
seconds after header compressor had
started.
All stop
While header compressor stopped,
current flowed more than the specified
amount.
All stop
Compressor 1 case thermostat performed
protective operation.
Check item (position)
• Misconnection of Ps sensor and Pd sensor connectors
• Check connection of Ps sensor connector.
• Check Ps sensor error.
• Check compression error of compressor.
• Check 4-way valve error.
• Check outdoor P .C. board (I/F) error.
• Check SV4 circuit error.
• Check connection of Pd sensor connector.
• Check Pd sensor error.
• Check outdoor P .C. board (I/F) error.
• Check power voltage.
• Check power noise.
• Check outdoor P .C. board (I/F) error.
• Check power voltage. (AC220–240V ± 10%).
• Check compressor error.
• Check cause of abnormal overload operation.
• Check outdoor P .C. board (IPDU) error.
• Check compressor error.
• Check power voltage. (AC220–240V ± 10%).
• Check cable of compressor and phase-missing.
• Check connector/terminal connection on IPDU P .C. board.
• Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
• Check outdoor P .C. board (IPDU) error.
• Check cabling of current detection circuit system.
• Check outdoor P .C. board (IPDU) error.
• Check compressor 1 case thermo circuit.
(Connector, cable, P .C. board)
• Check full opening of service valve. (Gas and liquid side)
• Check outdoor PMV clogging.
• Check SV4 circuit leakage.
• Check miscabling/misinstallation of SV4.
• Check valve open status of indoor PMV.
• Check 4-way valve error.
• Check refrigerant shortage.
• Check SV5 leak.