Toshiba MiNi-SMMS MCY-MAP0501HT Service Manual page 118

Mini-super modular multi system
Hide thumbs Also See for MiNi-SMMS MCY-MAP0501HT:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Wired
remote
controller Check code
Auxiliary code
F01
F02
F03
F04
F04
F06
F06
F07
F07
F08
F08
F10
F12
F12
01: TS1
F13
F13
01: Compressor 1
F15
F15
F16
F16
Detected
Check code
AI-NET
position
name
central control
remote controller
OF
Indoor unit Indoor TCJ
sensor error
Od
Indoor unit Indoor TC2
sensor error
93
Indoor unit Indoor TC1
sensor error
19
I/F
TD1 sensor
error
18
I/F
TE1 sensor
error
18
I/F
TL sensor error
1b
I/F
TO sensor error
OC
Indoor
Indoor TA
sensor error
A2
I/F
TS1 sensor
error
43
IPDU
TH sensor error
18
I/F
Outdoor temp
sensor
miscabling
(TE1, TL)
43
I/F
Outdoor
pressure
sensor
miscabling
(Pd, Ps)
Status
Error detection condition
Corresponding
• Resistance value of sensor is
unit only stops
infinite or zero. (Open/Short)
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short)
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
During operation of compressor
in HEAT mode, the TE1
detection temp was higher than
that of TL by the specified value
continued for 3 minutes or more.
All stop
High-pressure Pd sensor and
low-pressure Ps sensor were
exchanged, or output voltages
of both sensors are zero.
Check item (position)
• Check connection/cabling of TCJ sensor connector.
• Check characteristics of TCJ sensor resistance value.
• Check indoor P .C. board error.
• Check connection/cabling of TC2 sensor connector.
• Check characteristics of TC2 sensor resistance value.
• Check indoor P .C. board error.
• Check connection/cabling of TC1 sensor connector.
• Check characteristics of TC1 sensor resistance value.
• Check indoor P .C. board error.
• Check connection of TD1 sensor connector.
• Check characteristics of TD1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TE1 sensor connector.
• Check characteristics of TE1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TL sensor connector.
• Check characteristics of TL sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TO sensor connector.
• Check characteristics of TO sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection/cabling of TA sensor connector.
• Check characteristics of TA sensor resistance value.
• Check indoor P .C. board error.
• Check connection of TS1 sensor connector.
• Check characteristics of TS1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• IGBT built-in temp sensor error
→ Exchange IPDU P .C. board.
• Check installation of TE1 sensor and TL sensor.
• Check characteristics of TE1 and TL sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of high-pressure Pd sensor connector.
• Check connection of low-pressure Ps sensor connector.
• Check pressure sensors Pd and Ps error.
• Check outdoor P .C. board (I/F) error.
• Check compression error of compressor.