User Options - Worcester 24CDi Instruction Manual

Digistat programmable 24 hour room thermostat system
Table of Contents

Advertisement

User Options

User Options (shown in table below) can be
accessed from Auto or Man by pressing < and >
simultaneously for 3 seconds.
Once you have
accessed the User
Options Menu press
> to scroll through
selectable options.
The settings for each
option can be
changed by pressing
+ or - as required.
Pressing > accepts the change and moves to the
next option.
NOTE: To exit User Options press < and >
simultaneously for 3 seconds.
Alternatively, not press-
ing any buttons for 2
minutes will cause the
Programmer to return
to Auto.
This figure opposite
shows option "01 24"
(24 hour clock).
Only options that have
been accepted by
pressing > will be changed.
Option
Description of Option
01
Change clock 12h/24h
02
Change pre-set program
03
Change number of program
events per day
04
Switch on/off daylight saving
time change
05
Adjust date and time
06
Change temperature offset °C
07
Restore pre-set program
08
Disable OFF function
09
Access protection lock
OPERATING & INSTALLATION
6
INSTRUCTIONS
Option 01 Change from 24hr to 12hr clock.
Enter user options, select option 01 and use + and
– keys to select desired option, 12 = 12hr and 24 =
24hr. Press > to accept change.
Option 02 Change to program 1, 2 or 3.
Enter user options, select option 02 and use + and
– keys to select desired program 1, 2 or 3.
1 = program 1, 2 = program 2 and 3 = program 3.
Press > to accept change.
Preset programs 2 and 3 are shown below:
Pre-set Program 2 (Home for lunch)
24 hour
Event
Time
Temperature 21
At 06:30 the heating raises the temperature to 21°C.
At 08:30, the temperature set point is dropped to
16°C, until 12:00 when the heating raises the
temperature to 21°C. The temperature stays at 21°C
until 14:00 when it drops to 16°C. At 16:30 the heat-
ing raises the temperature to 21°C where it stays
until 22:30 when the temperature drops down to a
setback temperature of 10°C until 06:30 when the
cycle repeats the next day.
Min Max Default
12
24
24
1
3
1
2,4 or 6
6
On
Off
On
Factory set
-5
5
0
On
Off
Off
On
Off
On
On
Off
Off
DIGISTAT PROGRAMMABLE 24 HOUR
ROOM THERMOSTAT SYSTEM
8 716 114 518a (09.07)
DIGISTAT
USER OPTIONS
1
2
3
4
6:30 8:30 12:00 14:00 16:30 22:30
16
21
16
5
6
21