Performance Data - Payne PH1S Manual

Split system heat pump with air handling unit
Table of Contents

Advertisement

OUTDOOR UNIT
PH1S
090
NOTES:
1. Gross cooling capacity is based on 67 F wb, 80 F db air entering in-
door unit and 95 F db air entering outdoor unit.
OUTDOOR
INDOOR
AIRFLOW
UNIT
UNIT
(Cfm)
PH1S
PF1B
090
090
3000
Cap. — Integrated Heating Capacity (1000 Btuh) — includes indoor-
fan motor heat and effects of defrost.
kW
— Total Compressor Motor Power Input
PH1S090 WITH PF1B090
Airflow Air Entering Indoor Unit — Cfm/BF
Temp (F)
2250/0.09
Air Ent
Outdoor
Temp Air Entering Indoor Unit — Ewb (F)
Unit
72
67
62
TC
96.9 89.1 81.9 101.0 93.3 86.7 104.0 95.9 90.9
85
SHC 48.7 60.5 72.2
kW
6.44 6.24 6.06
TC
92.6 85.1 78.2
95
SHC 47.1 58.9 70.3
kW
7.03 6.80 6.58
TC
90.3 83.1 76.3
100
SHC 46.2 58.0 69.4
kW
7.32 7.07 6.84
TC
88.0 81.0 74.3
105
SHC 45.3 57.2 68.4
kW
7.60 7.34 7.08
TC
83.3 76.5 70.4
115
SHC 43.6 55.4 66.4
kW
8.17 7.86 7.58
TC
78.3 71.8 66.3
125
SHC 41.8 53.5 64.1
kW
8.71 8.36 8.05

PERFORMANCE DATA

NOMINAL CAPACITIES
INDOOR UNIT
PF1B
090
INTEGRATED HEATING CAPACITIES
-10
0
10
Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW
21.7
3.4
30.4
3.8
39.4
LEGEND
COMBINATION RATINGS
GROSS CAPACITIES — COOLING
3000/0.12
3750/0.14
72
67
62
72
67
53.8
69.0 82.9
58.5 76.6 90.2
6.54
6.34 6.18
6.60
6.41 6.27
96.4
89.0 82.8
98.8
91.5 86.8
52.2
67.4 80.6
56.8
75.0 86.8
7.14
6.93 6.73
7.21
7.00 6.86
94.0
86.8 80.9
96.3
89.2 84.9
51.3
66.5 79.4
55.9
74.0 84.9
7.44
7.21 7.00
7.51
7.29 7.14
91.6
84.5 78.8
93.7
86.8 82.8
50.5
65.6 78.0
55.1
73.1 82.8
7.74
7.48 7.26
7.81
7.57 7.41
86.4
79.7 74.9
88.4
81.9 79.0
48.7
63.7 74.9
53.3
71.1 79.0
8.30
8.01 7.79
8.39
8.11 7.98
81.1
74.7 71.0
83.0
76.8 74.7
46.9
61.8 71.0
51.5
68.9 74.7
8.86
8.52 8.32
8.95
8.63 8.51
AIRFLOW
GROSS COOLING
(Cfm)
CAPACITY (Btuh)
3000
2. Net heating capacity is based on 70 F db air entering indoor unit and
47 F db, 43 F wb air entering outdoor unit. Includes indoor fan heat
and defrost effects.
TEMPERATURE OF AIR ENTERING OUTDOOR UNIT (F db)
17
20
30
Cap.
4.3
45.8
4.6
48.3
4.8
56.2
NOTES:
1. To obtain total outdoor unit power, add outdoor fan kW shown to
compressor draw: PH1S090 — .96 kW.
2. Ratings are without supplementary heat and are based on 70 F db
air entering indoor unit. Wet-bulb temperature entering outdoor unit
varies with dry bulb; at 47 F db, wb is 43 F; at 17 F db, wb is 15 F.
BF
— Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input, Total
62
Ldb — Leaving Dry Bulb
Lwb — Leaving Wet Bulb
SHC — Sensible Heat Capacity, Gross (1000 Btuh)
TC
— Total Capacity, Gross (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
Below 80 F db, subtract (Corr Factor x Cfm) from SHC.
Above 80 F db, add (Corr Factor x Cfm) to SHC.
BYPASS
FACTOR
0.03
0.06
0.09
0.12
0.15
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (db – 80)
3. Formulas:
t
= t
ldb
edb
t
= wet-bulb temperature corresponding to enthalpy of air
lwb
leaving indoor coil (h
h
= h
lwb
ewb
where
h
ewb
4. Capacities are based on 25 actual ft (40 equivalent ft) of intercon-
necting piping sized to the outdoor unit field connections. (Equivalent
length is equal to the actual length plus a 50% allowance for fitting
losses.)
11
NET HEATING
CAPACITY (Btuh)
89,000
40
47
kW
Cap.
kW
Cap.
kW
Cap.
5.3
75.9
5.9
83.4
6.3
LEGEND
ENTERING-AIR DRY-BULB TEMP (F)
79
78
77
76
81
82
83
84
Correction Factor
1.07
2.13
3.20
4.27
1.03
2.07
3.10
4.14
1.00
2.00
3.00
4.00
0.97
1.94
2.90
3.87
0.94
1.87
2.81
3.74
sensible heat capacity (Btuh)
1.10 x cfm
)
lwb
total capacity (Btuh)
4.5 x cfm
= enthalpy of air entering indoor coil
83,000
50
60
kW
Cap.
kW
86.8
6.5
98.4
7.1
75
under 75
85
over 85
5.34
5.17
Use formula
5.01
given.
4.84
4.68