LIQUID LINE SOLENOID VALVE (PH1S090 only)
Addition of a liquid solenoid valve (LLSV) is recommended
when the piping system length exceeds 75 feet. The LLSV must
be a bi-flow type suited for use in heat pump systems.
The recommended valve is Sporlan model CB14S2 (5/8-in.
ODF, 7/8-in. ODM). This solenoid valve requires Sporlan part
no. MKC-2 coils that must be purchased locally. Wire the sole-
noid valve in parallel with the compressor contactor coil.
The LLSV must be installed at the outdoor unit with the flow ar-
row pointed toward the outdoor unit (in-flow direction for the
heating mode.)
MINIMUM OUTDOOR-AIR
OPERATING TEMPERATURE*
SATURATED
UNIT
COMPR
CONDENSING
PH1S
CAP. (%)
TEMP (F)
090
100
95
*Applies to cooling mode of operation only.
OUTDOOR UNIT
PH1S
090
*Vertical distance between indoor and outdoor units.
FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA — INDOOR UNIT
UNIT
PF1B
Qty...Part No.
090
APPLICATION DATA (cont)
MINIMUM OUTDOOR
TEMPERATURE (F)
Head Pressure
Std Unit
Control
55
20
MAXIMUM VERTICAL SEPARATION*
INDOOR UNIT
PF1B
090
TXV
DISTRIBUTOR
Qty...Part No.
1...SVE-8
REFRIGERANT CHARGE AND
OUTDOOR
UNIT
PH1S
090
090
L — Liquid Line
V — Vapor Line
*If there is a vertical separation between indoor and outdoor units, see
Maximum Vertical Separation table.
†Approximately 4 elbows assumed in determining pipe sizes.
Maximum length of interconnecting piping is 100 feet.
**Approximate system charge is for estimating only. It includes charge
requirements for one outdoor unit, matching indoor coil, and length of
interconnecting piping shown. System should be charged in accor-
dance with installation instructions.
Above Outdoor Unit
65
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
1...1657
20
PIPING SELECTION DATA*
LENGTH OF PIPING (ft)†
0-25
26-60
61-100
Line Size (in. OD)
L
V
L
V
L
1
1
1
5
1
1
5
2
8
8
8
8
APPROXIMATE SYSTEM
CHARGE. R-22 (lb)**
19.5
26
DISTANCE (FT)
Indoor Unit
Below Outdoor Unit
15...
1
4
MAXIMUM
LIQUID
LINE
(in. OD)
V
1
1
5
8
8
MAXIMUM
CHARGE
32
35
75
NOZZLE
Qty...Part No.
1...C6